TFP172
Page 2 of 4
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) and 3/32
inch (2,4 mm) for the 286°F (141°C) tem-
perature ratings.
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum to maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1.
Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2.
With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3.
Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A.
After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B.
Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
Nm).
Step C.
After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
Components:
1/2" NPT
1
5
2
3
4
2"
(50,8 mm)
Frame
Button
Sealing
Assembly
*
6
2 -
-
3
-
1
*
-
6
Deflector
Compression
Screw
-
5
4 - Bulb
2-7/8" (73,0 mm) DIA.
1-3/8"
(34,9 mm)
2"
(50,8 mm)
WRENCH
FLATS
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
STYLE 15 or 20
RECESSED
ESCUTCHEON
7/16" (11,1 mm)
NOMINAL MAKE-IN
Pipe thread connections per ISO 7-1
can be provided on special request.
**
DEFLECTOR
*
Temperature rating is
indicated on Deflector.
DEFLECTOR
*
*
ESCUTCHEON PLATE
SEATING SURFACE
**
**
1/2"
NPT
UPRIGHT
CROSS SECTION
PENDENT
RECESSED PENDENT
WRENCH RECESS
(USE ONLY
END "A")
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Summary of Contents for VicFlex AH1
Page 26: ......
Page 27: ......
Page 44: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 75: ......
Page 76: ......
Page 93: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 124: ......
Page 125: ......
Page 142: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 153: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 184: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 215: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...