Step 8.
Screw on the Cover Plate/
Retainer Assembly until the Retainer
(shown in Figure 2) or the Air and Dust
Seal (shown in Figure 5) contacts the
ceiling. Do not continue to screw on the
Cover Plate/Retainer Assembly so that
it lifts a ceiling panel out of its normal
position. If you cannot engage the
Cover Plate/Retainer Assembly with
the Support Cup or you cannot engage
the Cover Plate/Retainer Assembly suf-
ficiently to contact the ceiling, you must
reposition the Sprinkler Fitting.
Care and
Maintenance
The TYCO Series RFII 5.6 K-factor,
“Royal Flush II” Concealed Pendent
Sprinklers must be maintained and
serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2.
This air gap is necessary for proper
operation of the sprinkler. If the ceiling
requires repainting after sprinkler
installation, ensure that the new paint
does not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
Exercise care to avoid damage to sprin-
klers before, during, and after instal-
lation. Replace sprinklers damaged
by dropping, striking, wrench twist-
ing, wrench slipping, or the like. Also,
replace any sprinkler that has a cracked
bulb or that has lost liquid from its bulb.
(Refer to the Installation section.)
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace it immediately.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufac-
turer regarding any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: Series RFII (specify SIN),
K=5.6, “Royal Flush II” Pendent Sprin-
klers (specify) temperature rating and
(specify) finish, P/N* (specify):
155°F (68°C)
200°F (93°C)
TY3531
51-792-1-155
51-792-1-200
TY3551
51-790-1-155
51-790-1-200
* Use Suffix “I” for ISO 7-1 connection; for example,
51-792-1-155-I
Separately Ordered Cover Plate/
Retainer Assembly:
Specify: (temperature rating from
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify).
139°F (59°C)(a) 165°F (74°C)(b)
Grey White
(RAL9002) . . . . 56-792-0-135 56-792-0-165
Brass . . . . . . . . . . 56-792-1-135 56-792-1-165
Pure White (c)
(RAL9010) . . . . 56-792-3-135 56-792-3-165
Signal White
(RAL9003) . . . . 56-792-4-135 56-792-4-165
Jet Black
(RAL9005) . . . . 56-792-6-135 59-792-6-165
Brushed
Chrome . . . . . . . . 56-792-8-135 56-792-8-165
Chrome . . . . . . . . 56-792-9-135 56-792-9-165
Custom . . . . . . . . 56-792-X-135 56-792-X-165
(a) For use with 155°F (68°C) sprinklers.
(b) For use with 200°F (93°C) sprinklers.
(c) Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075
Air and Dust Seal
Specify: Air and Dust Seal,
P/N 56-908-1-001
SUPPORT
CUP
SPRINKLER
AIR
AND DUST
SEAL
COVER
PLATE
LIP OF
RETAINER
FACE OF
CEILING
ORIENT
SEAL
BEVEL AS
SHOWN
COVER
PLATE
RETAINER
ASSEMBLY
FIGURE 5
OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551)
Summary of Contents for VicFlex AH1
Page 26: ......
Page 27: ......
Page 44: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 75: ......
Page 76: ......
Page 93: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 124: ......
Page 125: ......
Page 142: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 153: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 184: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Page 215: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...