Function Parameter Table VD520 Series Inverter User Manual
- 66 -
Time
F9-35
Fault DO Action
Selection
During the Fault
Automatic
Reset
0: No action
1: Action
0
○
F9-36
Fault Protection
Action Selection
1
Unit’s digit: motor overload (11)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: input phase loss (13)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: output phase loss
(14)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: external fault (17)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten thousand’s digit: communication
abnormal (18)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
0x00000
○
F9-37
Fault Protection
Action Selection
2
Unit’s digit: reserved
Ten’s digit: parameter read-write
abnormal (21)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: running time reached
(27)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: reserved
Ten thousand’s digit: reserved
0x00000
○
F9-38
Fault Protection
Action Selection
3
Unit’s digit: user-defined fault 1 (35)
0: Coast to stop
1: Stop according to stop mode
0x00000
○