VD520 Series Inverter User Manual Parameter Description
- 113 -
series motor parameters.
If t
he site can’t tuned for asynchronous motor, can according to the parameters given by motor
manufacturer, input the above corresponding function code.
F2-26
Tune Selection
0: No operation
1: Asynchronous motor static tuning
2: Asynchronous motor complete tuning
0
◎
0: No operation, namely the tuning is prohibited.
1: Asynchronous motor static tuning, suitable for the occasion of asynchronous motor and load is not
easy to release, but can’t be complete tuning.
Asynchronous motor static tuning before, must be properly set motor type and motor nameplate
parameters F2-00~F2-05. Asynchronous motor static tuning, inverter can obtain F2-06~F2-08 three
parameters.
Action description: set the function code to 1, and then press RUN key, inverter will conduct static
tuning.
2: Asynchronous motor complete tuning
In order to guarantee the dynamic control performance of the frequency inverter, please select
complete tuning, the motor must disconnect with load, and to keep the motor for the idling condition.
In the process of complete tuning, inverter conduct to static tuning first, and then according to the
acceleration time F0-18 to the 80% of rated motor frequency, after a period of time, accordance with
the deceleration time F0-19 slowing down and end tuning.
Before asynchronous motor is complete tuning, you need to setup the motor type and motor
nameplate parameters F2-00~F2-05.
Asynchronous motor complete tuning, frequency inverter can get F2-06~F2-10 five motor parameters,
vector control current loop PI parameter F3-13~F3-16.
Action description: set the function code to 2, and then press the RUN button, inverter will be
complete tuning.