47
P 103
Desired space temperature in the first period
[
o
C]
Setting the desired space temperature in the first HC period
P 104
Second HC period switched on
[h:min.]
Setting the switching-on time of the second period for HC heating
P 105
Second HC period switched off
[h:min.]
Setting the switching-off time of the second period for HC heating
P 106
Desired space temperature in the second period
[
o
C]
Setting the desired space temperature in the second HC period
P 107
Third HC period switched on
[h:min.]
Setting the switching-on time of the third period for HC heating
P 108
Third period HC switched off
[h:min.]
Setting the switching-off time of the third period for HC heating
P 109
Desired space temperature in the third period
[
o
C]
Setting the desired space temperature in the third HC period
P 110
HC time schedule reset
By this parameter activation the time regime is reset into manufacturer’s setting.
Value 1 – activation
P 111
Desired space temperature in attenuation
[
o
C]
Setting the desired space temperature at the time outside the time period
P 120
Setting the day of time schedule for HW
Setting the day of the week required for setting the individual HW heating periods
Value from1 to 7 – corresponds to days from Monday to Sunday and we set it separately every
day
Value 0 – setting all days at once
P 121
First period HW switched on
[h:min.]
Setting the time of switching-on the first period for HW heating
Note: It isn’t necessary to use the second and third period
P 122
First period HW switched off
[h:min.]
Setting the time of switching-off the first period for HW heating
P 123
Desired HW temperature in the first period
[
o
C]
Setting the desired HW temperature in the first period
Note: In application with HW thermostat the value must correspond to the temperature set on HW
thermostat.
P 124
Second period HW switched on
[h:min.]
Setting the time of switching –on the second period for HW heating
P 125
Second period HW switched off
[h:min.]
Setting the time of switching -off the second period for HW heating
P 126
Desired HW temperature in the second period
[
o
C]
Setting the desired HW temperature in the second period
Note: In application with HW thermostat the value must correspond to the temperature set on HW
thermostat.
P 127
Third period HW switched on
[h:min.]
Setting the time of switching –on the third period for HW heating
P 128
Third period HW switched off
[h:min.]
Setting the time of switching –off the third period for HW heating
P 129
Desired HW temperature in the third period
[
o
C]
Setting the desired HW temperature in the third period
Note: In application with HW thermostat the value must correspond to the temperature set on HW
thermostat.
P 130
HW Hysteresis
[
o
C]
This value relates to the desired HW temperature. In case the HW temperature has dropped by
this value below the HW set desired value HW heating will start again.