Vertiv™ NetSure™ HVT F02 CK1 Power System User Manual
19
Port
Sn
Name
Description
Max. Connected Wire Spec.
I
2
C port
1
VCC
1.5mm
2
or 16AWG
2
SDA
3
SCL
4
GND
DI1
1
Passive dry contact input terminal
1.5mm
2
or 16AWG
2
Passive dry contact input terminal
DI2 ~ 4
1 ~ 2
Same to DI1
DI5
1
+
Active signal contact input te
1.5mm
2
or 16AWG
2
-
Active signal contact input terminal -
DI6
1
+
Active dry contact input te
2
-
Active dry contact input terminal -
RS485-1
1
A
RS485A, used to connect battery detector BM400V1
1.5mm
2
or 16AWG
2
B
RS485B, used to connect battery detector BM400V1
3
PE
PE
1.5mm
2
or 16AWG
RS485-2
1
A
RS485A, used to connect the power distribution control of
AC distribution cabinet, DC distribution cabinet and
secondary-level distribution cabinet
1.5mm
2
or 16AWG
2
B
RS485B, used to connect the power distribution control of
AC distribution cabinet, DC distribution cabinet and
secondary-level distribution cabinet
3
PE
PE
RS485-3
1
A
RS485A, used to connect the power distribution control of
the PDU cabinet
1.5mm
2
or 16AWG
2
B
RS485B, used to connect the power distribution control of
the PDU cabinet
3
PE
PE
CAN1
1
H
CAN+, used to connect the rectifier
1.5mm
2
or 16AWG
2
L
CAN-, used to connect the rectifier
CAN2
1
H
CAN+, reserved
1.5mm
2
or 16AWG
2
L
CAN-, reserved
DO1
1
NO
DO1, normally open dry contact
1.5mm
2
or 16AWG
2
COM
DO1 common port
3
NC
DO1, normally closed dry contact
DO2 ~ DO8
1 ~ 3
NO, COM, NC
Same to DO1
RS232
1 ~ 9
See Figure 1.17
See Figure 1.17
/
The definition of dry contact function can be set through controller or WEB browser. See
M822E Controller User Manual
for
details.
The specifications of the dry contact interface are as follows:
Digital quantity input: DI1 ~ DI4, passive dry contact.
DI5 ~ DI6 opto-isolation, the alarm and power frequency are definable (high power level: 20V ~ 60V, low power level: less than 1V).
Digital signal output: DO1 ~ DO8, 8-route transfer contact, relay isolation; Maximum: 30Vdc/1A, 125Vac/0.5A, 60W; minimum:
10uA@10Vdc. Alarms are definable. (Note that DO8 is used as fault indicator alarm)