Vertiv™ NetSure™ HVT F02 CK1 Power System User Manual
2
Cabinet
Connector
Terminal Spec
Remarks
PD380/800AFH-3-Y2 AC
distribution cabinet
AC input MCB (3P isolator, N
line not changed)
Eight M12 bolts, (one route input) (suggested
cable CSA 240mm
2
)
Phase line and N line of AC
power
Grounding busbar
One M10 bolt (suggested cable CSA 120mm
2
)
Earth terminal connected to
machine room
The CSA of DC cable depends on the current flowing through the cable and the allowable voltage drop. The recommended load
peak capacity is 1/2 to 2/3 of the MCB/fuse capacity.
The earth cable CSA of DC distribution cabinet is listed in Table 1.3.
Table 1.3
Earth cable CSA of DC distribution cabinet
Connector
Terminal Spec
Cable CSA
Grounding busbar
M10 bolt (1 piece)
Max. cable CSA: 240mm
2
The battery cable CSA is listed in Table 1.4.
Table 1.4
Battery cable CSA
Battery Fuse Rated Current
Max. Battery Current
Min. Cable CSA
Specs Of Cable Connector
Max. Cable Length (Allowable Voltage
Drop: 3.0v)
1250A
1200A
2 × 240mm
2
M12 OT terminal
60m
1600A
1500A
2 × 240mm
2
M12 OT terminal
60m
Note:
1. The specs are applicable at ambient temperature of 25°C. If the temperature is higher than this, the CSA of the cable should be increased.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core flame retardant cable as battery cable
The load cable CSA is listed in Table 1.5.
Table 1.5
Load cable CSA
Load Route Rated
Current
Max. Output
Current
Min. Cable
CSA
Max. Cable Length (Volt Drop:
3.0V, With Min. CSA)
Max. Cable CSA
Max. Cable Length (Volt Drop: 3.0V,
With Max. CSA)
630A
500A
240mm
2
81m
2 × 240mm
2
163m
500A
400A
185mm
2
78m
2 × 240mm
2
201m
400A
320A
150mm
2
78m
2 × 150mm
2
157m
300A
240A
120mm
2
84m
2 × 150mm
2
209m
250A
200A
95mm
2
81m
2 × 150mm
2
252m
160A
120A
50mm
2
69m
75mm
2
105m
100A
80A
35mm
2
72m
75mm
2
157m
50A
40A
16mm
2
66m
25mm
2
105m
32A
25A
10mm
2
66m
16mm
2
108m
Note:
1. The specs are applicable at ambient temperature of 25°C. If the temperature is higher than this, the CSA of the cable should be increased.
2. The allowable max. current of the load shall be derated in accordance with the protection device rated cable of 80%.
3. Load route rated current value is only for typical value. The user needs to prepare appropriate cables according to the above data and the actual load rated
current value
The CSA of the system earth cable should be half of the maximum power distribution cable and not less than 95mm
2
. M10 bolt is
recommended for grounding busbar connection terminal.