Vertiv™ NetSure™ HVT F02 CK1 Power System User Manual
11
If optional AC distribution cabinet is not configured, use the earth cables to connect the earth terminal of the DC distribution
cabinet to the earth terminal of the rectifier cabinet, and then connected to the grounding busbar of the equipment room.
1.4.4
Connecting AC Input Cables
Connection requirements
1. The AC input cables are wired from the user distribution switch, and connected to the output terminal when the power is to be
switched on. The AC input is fitted with protection devices for over-current, short circuit and lightning protection devices. The
capacity of the distribution switch should not be less than 1.5 ~ 2 times of the load capacity.
2. The yellow, green, red, and light blue AC cables correspond respectively to the AC phase A, B, C and neutral lines. If the cables
are of the same color, they should be numbered or identified with insulating tape of different colors at both cable ends.
3. The AC cables should be wired separately from the DC cables, with separation exceeding 150mm.
4. No splice, damage or scratch on the cables is permitted.
Connection with optional AC distribution cabinet
1. Connect the AC distribution cabinet and the user’s distribution switch outside the power system.
The AC cables can enter the system from either the top of AC distribution cabinet through cabling rack or the bottom of AC
distribution cabinet through trenching. After the AC input cables are led into the cabinet, connect them to the MCBs, as shown in
Figure 1.11.
Figure 1.11
Connection of AC input cables and AC distribution cabinet
2N
1N
2C
2B
2A
1C
1B
1A
AC input 1
AC input 2
PD380/630AFH-3-Y2 rear view (MCB)
2. Select the AC cables which connected to the AC distribution cabinet and the rectifier cabinet.
According to the position of the rectifier cabinet and the AC cabinet, the length of each cable is determined according to the
actual routing path.
3. The cable solder less terminal is not pressed. Perform pressure welding after cutting cable to the proper length
。