Appendix
Vertiv | Liebert CRD10 | User Manual
110
Lv.1 Menu
Lv.2 Menu
Parameter
Run Information
Teamwork Information
#00 Unit Status
#01 Unit Status
#02 Unit Status
#03 Unit Status
#04 Unit Status
#05 Unit Status
#06 Unit Status
#07 Unit Status
#08 Unit Status
#09 Unit Status
#10 Unit Status
#11 Unit Status
#12 Unit Status
#13 Unit Status
#14 Unit Status
#15 Unit Status
Alarm Information
Alarm Status
--
Alarm History
--
Temp/Hum Setting
Temp Setting
Supply Avg Temp SP, Default 23C (73.4F), Range 15 to 32C (59 to 89.6F)
Return Avg Temp SP, Default 32C (89.6F), Range 18 to 40C (64.4 to 104F)
Remote Avg Temp SP, Default 23C (73.4F), Range 15 to 32C (59 to 89.6F)
Hum Setting
Supply Avg Hum SP, Default 50%, Range 20% to 60%
Parameter Setting
Teamwork Setting
Teamwork Mode
Unit Address
Units Quantity
Standby Quantity
Rotation Quantity
Rotation Cycle
Rotate Daily
Rotate At
Manual Rotate
Run Standby Delay
Cascade Mode
Cascade Start Require
Cascade Stop Require
Cascade Max Require
Cascade Start Delay
Cascade Stop Delay
Cascade Min Time
Alarm Setpoint
Sup High Temp Alarm SP, Default 27C (80.6F), Range 20 to 35C (68 to
95F)
Sup Low Temp Alarm SP, Default 8C (46.4F), Range 5 to 20C (41 to 68F)
Rtn High Temp Alarm SP, Default 40C (104F), Range 30 to 45C (86 to
113F)
Rtn Low Temp Alarm SP, Default 18C (64.4F), Range 5 to 25C (41 to 77F)
Rtn High Hum Alarm SP, Default 60%, Range 50% to 99%