Electrical Installation
Vertiv | Liebert CRD10 | User Manual
55
4.2.4
Connecting the Power Cable of the outdoor unit
The outdoor unit (CCD10) is controlled by indoor unit, the specific location of the power port of the outdoor
unit is also shown in Figure 4-1. Connect the outdoor breaker terminals L, N (or L1, L2) and PE (or G) to their
respective counterparts of the outdoor respectively. The detailed specification of cable, please refer to
CCD10 user manual.
4.3
Connection of the Control Cables
The location of the terminal block for cable connections in the site is shown in Figure 4-1. The amplified view
of the terminals is shown in Figure 4-3.
(UL)
(CE)
Figure 4-3 Amplified View of Terminal
NOTE: The connection personnel must take anti-static measures before connecting the control cables.
4.3.1
Water-Under-Floor Sensor
NOTICE!
Risk of clogged or leaking drain lines and leaking water-supply lines. Can cause equipment and
building damage.
This unit requires a water drain connection. Drain lines must be inspected at start-up and periodically,
and maintenance must be performed to ensure that drain water runs freely through the drain system
and that lines are clear and free of obstructions and in good condition with no visible sign of damage
or leaks. This unit may also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the unit.
Water leakage can result in catastrophic and expensive building and equipment damage and loss of
critical data center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
We recommend installing a monitored fluid-detection system to immediately discover and report
coolant-fluid system and condensate drain-line leaks.
The unit accessories are equipped with a water-under-floor sensor, connect one end of the sensor to
L3, L4/L3, N3: Low Ambient Kit Heating Belt
72, 73: LLSV
75, 76: Common Alarm
37, 38: Remote Shutdown
51, 24: Water Under Floor
CAN-1, CAN-2: CAN Communication
TB3: Rack Sensor
CAN1 CAN2
TB3