Product Overview
Vertiv | Liebert CRD10 | User Manual
7
1.4
Basic Performance Parameters
The basic performance parameters of the Liebert CRD10 are given in Table 1-4.
Table 1-4 Performance Parameters
Certification
UL
CE
Unit
CRD100
CRD101
CRD102
Model
CRD100-0D00A
CRD101-0D00A
CRD102-1D00A
Voltage/Frequency
208/230V 1PH 60Hz
208/230V 3PH 60Hz
230V 1PH 50/60Hz
Cooling Capacity (kW)
10.0
10.0
10.0
Heating Capacity (kW)
-
-
2.0
Power Input(kW)
3.2
3.2
3.2(Without the heater)
Full Load Current (A)
-
-
38 (With the heater)
28 (Without the heater)
MCA (A)
29
21
-
MOP (A)
40
30
-
Test Condition:
Return air 29.4°C (85°F), 32% RH & 35°C (95°F) Outdoor temperature.
Note: The allowed thermal load shall not be lower than 20% of nominal air conditioner cooling capacity.
Lower thermal load will drive to imprecise temperature and humidity control and frequent compressor(s)
switch on/off.
The performance data of CRD100 and CRD101 rated with the AHRI stand 1360 are given in Table 1-5.
Table 1-5 Performance data of AHRI
Model Number
CRD100-0D00A
CRD101-0D00A
Voltage (Volts/Phase/Hz)
208/1/60
230/1/60
208/3/60
230/3/60
Net Total Cooling Capacity, kW (kBtuh)
10.0(34.1)
9.98(34.0) 10.32(35.2)
10.41(35.5)
Net Sensible Cooling Capacity, kW (kBtuh)
9.92(33.8)
9.96(33.9)
10.08(34.4)
10.12(34.5)
Net Sensible Coefficient of Performance (NSenCOP),
kW/kW
3.57
3.62
3.69
3.71
Unit Airflow, ACFM
1960
1961
1897
1898
Unit Airflow, SCFM
1896
1887
1835
1836
Ext. Static Pressure, Pa
0.0
0.0
Humidification
None
None
Refrigerant
R-410A
R-410A
Return Air Conditions 95°F DB, 52°F DP (35°C DB, 11.1°C DP) 32% RH
Outdoor Ambient Temperature 95°F (35°C)
Certified in accordance with the AHRI Datacom Cooling Certification Program at AHRI Standard 1360 Standard
Rating Conditions. Certified units may be found in the AHRI Directory at