Product Overview
Vertiv | Liebert CRD10 | User Manual
12
temperature, humidity, door closure, contact closure and leak detection. Sensor tab menus permit configuring
sensors and putting them in user-configured order for easier checking of high-priority conditions. Sensor data is
available via SNMP and the Web user interface.
1.6.10
Remote Temperature Sensor
The Liebert CRD10 models are compatible with multiple temperature sensors based on the requirement. Each
unit can be connected with up to maximum 10 temperature sensors.
1.6.11
Condensate pump
The Liebert CRD10 models include a condensate pump which is used for drainage. The performance curve is
shown in Figure 1-11.
Note: Maximum recommended vertical rise is 5m(16.4ft.).
Figure 1-11 Performance curve of condensate pump
1.6.12
Liquid Line Solenoid Kit
The liquid line solenoid kit is a solenoid valve used to prevent refrigerant from condensing into liquid line in
condenser and pipe of outdoor when the unit is turned off at the condition of low ambient temperatu
re.
Figure 3-1 sh
ows the install location of solenoid valve in the system. Figure 1-12 shows the solenoid valve.
Figure 1-12 Solenoid Valve
Not Recommended
Performance curve