Commissioning Overview
Vertiv | Liebert CRD10 | User Manual
69
13.
Ensure that all control system settings are correct and that there are no alarms.
14.
Once the system is operating under load, carry out the following checks:
•
Verify that the fans are operating properly
.
•
Ensure that the temperature and relative humidity are being reached, and the heating steps operate when
required.
5.4.2
Automatic Restart
If requested, the unit will automatically restart on the return of power after a power supply interruption. If
the power interruption is expected to last several hours, to avoid an automatic cold restart of the
compressor stop the unit before the interruption and on the return of power, allow the compressor to
preheat before restarting the unit.