Table 17: TEC3000 Series BACnet MS/TP or wireless thermostat controllers
Specification
Description
Relay contact rating(On/Off, floating,
or staged economizer control models)
19 VAC to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Fan relay output rating(On/Off,
floating, and proportional control
models)
19 VAC to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Auxiliary output rating/triac output
(On/Off, floating, and proportional
control models)
19 VAC to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Binary inputs
Dry contact across terminal COM to terminals BI1, BI2, or COS
Analog inputs
Nickel, platinum, A99B, 2.25k ohm negative temperature coefficient (NTC), 10,000
ohm NTC, 10,000 ohm NTC Type 3 across terminal COM to terminals R SEN or COS
Temperature sensor type
Local 1000 ohm platinum sensor
Wire size
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter)
MS/TP network guidelines
Up to 100 devices maximum per network automation engine (NAE);4,000 ft (1,219
m) maximum cable length, add repeaters to extend this length.
Wireless band
Direct-sequence spread-spectrum 2.4 GHz ISM bands
Transmission power
10 mW maximum
Transmission range
50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
Backlit display
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating control
40.0°F/4.5°C to 90.0°F/32.0°C
Temperature
range
Cooling control
54.0°F/12.0°C to 100.0°F/38.0°C
Temperature
±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Accuracy
Humidity (On/
Off, floating, and
proportional control
models)
±5% RH from 20% to 80% RH at 50°F to 90°F (10°C to 32°C)
Minimum deadband
2F°/1C° between heating and cooling
Occupancy sensor motion detection
(occupancy sensing models)
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);based on a clear
line of sight
Operating
32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensing
Ambient
conditions
Storage
-22°F to 122°F (-30°C to 50°C); 95% RH maximum, noncondensing
UL Listed, File E27734, CCN XAPX, under UL60730
United States
Transmission complies with FCC Part 15.247 regulations for low power unlicensed
transmitters; transmitter identification FCC: OEJ-WRZRADIO
UL Listed, File E27734, CCN XAPX7 under E60730
Compliance
Canada
Industry Canada (IC) RSS-210;transmitter identification ZFR1810-1: IC: 279A-
WRZRADIO
Europe
TEC36xx-0x-000
CE Mark—Johnson Controls declares that this product is in compliance with the
essential requirements and other relevant provisions of the Radio Equipment
Directive (RED), the Low Voltage Directive (LVD), the EMC Directive, and the RoHS
Directive.
Australia and New
Zealand
RCM Mark, Australia/NZ Emissions Compliant
Models without
occupancy sensor
0.75 lb (0.34 kg)
Shipping
weight
Models with
occupancy sensor
0.77 lb (0.35 kg)
Verasys System Product Bulletin