Table 20: VEC technical specifications
Specification
Description
Terminations
Input and output: fixed spade terminals
Sensor bus, zone bus, Modbus: 4-wire and 3-wire pluggable screw terminal blocks
Sensor bus tool port: RJ-12 6-pin modular jack
Field install option:
Input and output: fixed solder terminals
Sensor bus, zone bus, Modbus: 4-wire and 3-wire pluggable screw terminal blocks
Sensor bus tool port: RJ-12 6-pin modular jack
Mounting
Horizontal on single 35-mm DIN rail mount preferred, or screw mount on flat surface with
three integral mounting clips on the controller
Housing
Enclosure material: Polycarbonate Lexan SABIC EXL9330
Dimensions (H x W x D)
6.45 in. x 4.92 in. x 2.08 in. (164 mm x 125 mm x 53 mm) excluding terminals and
mounting clips
Weight
0.5 kg (1.1 lb)
United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment
FCC Compliant to CRF47, Part 15, Subpart B, Class A
Compliance
Canada: UL Listed, File E107041, CNN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment
Industry Canada Compliant, ICES-003
Europe: Johnson Controls declares that this product is also in compliance with the
essential requirements and other relevant provisions of the EMC Directive and Low
Voltage Directive Declared as Electronic Independently mounted control, suitable for DIN
rain mounting. Intended to mount in remote panel. Type 1.C (Micro-interruption), 330 V
rated impulse voltage. 125°C ball pressure test.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
Table 21: Zone Coordinator Controller
Specification
Description
Power requirements
Enclosure model:
120/240 VAC Primary 50/60 Hz, 24 VAC Secondary Transformer,
+10%/-15%, 400 mA, nominal 12 VA
Board-Only model:
24 VAC(15%), Primary 50/60 Hz, 24 VAC Secondary Transformer (±15%),
400 mA, nominal 12 VA, 12 VDC (+50%/-2%)
Addressing
Addressing is selectable by the MAC Address Switch: 8-position DIP switch using switches 1
through 7, valid address range 4 to 127
Installation environment
Protected, dry
Ambient operating
conditions
-40°C to 65°C (-40°F to 149°F); 0% to 95% RH, noncondensing
Ambient storage conditions
-40°C to 85°C (-40°F to 185°F); 0% to 95% RH, noncondensing
Power
Enclosure model:
One 3-position terminal block for 120/240 VAC supply power
Board-only model:
Removable terminal plug for 24 VAC supply power and removable
terminal plug for 12 VDC supply power
Shipping weight
Enclosure model:
2 kg (4.5 lb)
Board-only model:
227 g (8 oz)
Compliance
United States:
UL Listed 916/FCC Part 15, conducted and radiated
Europe:
CE Mark—Johnson Controls declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive and the Low
Voltage Directive.
25