Table 23: LC-VAC110x-0
Specification
Description
Input and output capabilities
Five universal inputs:
application-specific, three available modes (see application note
for wiring diagrams and usage):
•
Voltage input: 0 VDC to 10 VDC
•
Current sense input: 4 mA to 20 mA
•
Resistive inputs and dry contact inputs
Four binary inputs:
Defined as dry contact maintained
Three configurable outputs:
application-specific, two available modes:
•
Analog Output: 0 VDC to 10 VDC, 10 mA
•
Triac Output: 24 VAC, 0.5 A, externally sourced powered.
One utility output power port:
Ability to deliver 24 VAC
Four binary outputs (relays):
Single-pole, single-throw. Dry contacts rated 240 VAC.
•
UL: 240 VAC, 5 A resistive, 1.9 LA/11.1LRA, D300 pilot duty, 70°C/158°F, 30,000
cycles
•
IEC: 240 VAC, 3 A resistive, 3 A inductive, Cos=0.6, -4°F to 158°F (-20°C to 70°C),
100,000 cycles.
Note:
Reference all relay commons to the same pole of the supply circuit.
Two BO Triacs:
Output: 24 VAC or 240 VAC, 0.5 A, externally powered
Note:
Reference all triac commons to the same pole of the supply circuit.
Analog input/Analog output
resolution and accuracy
Analog input:
12-bit resolution
Analog output:
15-bit resolution, +/- 200 mV accuracy in 0 to 10 VDC applications
Terminations
Input/output: Fixed spade terminals
Sensor, system and modbus: 4-wire and 3-wire pluggable screw terminal blocks
Sensor Bus tool port: RJ-12 6-pin modular jack
Mounting
Horizontal on a single 35 mm DIN rail mount is preferred, or screw mount on flat surface
with three integral mounting clips on controller.
Mount the controller on a wall or DIN rail inside an enclosure (rated at least IP20).
Method to provide earthing
(Grounding)
Functional earthing: Terminal W44
Housing
Enclosure material: Polycarbonate Lexan SABIC EXL9330
Dimensions (H x W x D)
7.48 in. x 4.92 in. x 2.28 in. (190 mm x 125 mm x 58 mm) excluding terminals and
mounting clips
Weight
1.1 lb (0.5 kg)
United States:
cULus Listed, File E107041, CCN PAZC, UL 916, Energy Management FCC
Compliant to CRF47, Part 15, Subpart B, Class A
Compliance
Canada:
cULus Listed, File E107041, CNN PAZX7 CAN/CSA C22.2 No.205, Signal
Equipment
Industry Canada Compliant, ICES-003
Europe:
Johnson Controls declares that this product is also in compliance with the
essential
requirements and other relevant provisions of the EMC Directive and Low Voltage
Directive
Declared as Electronic Independently mounted control, suitable for DIN rail mounting.
Intended to mount in remote panel. Type 1.C (Micro-interruption) for relays,
2,500 V rated impulse voltage. 125°C ball pressure test.
Australia and New Zealand:
RCM Mark, Australia/NZ Emissions Compliant
Verasys System Product Bulletin