Table 18: Zone Damper and Bypass Damper Controllers
Specification
Description
Product code number
LC-ZEC310-0: Field installed, Zone Damper Controller
LC-BYP200-0: Field installed Bypass Damper Controller
Power supply requirement
24 VAC, nominal, 20 VAC minimum/30 VAC maximum, 50 Hz to 60 Hz, Class 2 power supply
(North America) or SELV (Europe)
Power consumption
10 VA, not including external load
VA ratings do not include any power supplied to the peripheral devices connected to binary
outputs (BOs) or configurable outputs (COs), which can consume up to 12 VA for each BO or
CO, for a possible total consumption of an additional 60 VA, maximum.
Ambient conditions
Ambient operating conditions: 0°C to 50°C (32°F to 122°F)
Ambient storage conditions: -40°C to 70°C (-40°F to 158°F)
Processor
RX630 32-bit Renesas
®
microcontroller
Memory
1 MB flash memory and 512 KB Random Access Memory (RAM)
Input and output capabilities
1 - Universal Input: Defined as 0 VDC-10 VDC, 4 mA-20 mA, 0-600 K ohm, or binary dry
contact
3 - BOs: Defined as 24 VAC Triac, internal power source
2 - COs: Defined as 0 VDC-10 VDC or 24 VAC Triac BO
Analog input/Analog output
accuracy
Analog input: 15-bit resolution on UIs
Analog output: 0 VDC-10 VDC ± 200 mV
Mounting
Mounts to damper shaft using single set screw and to duct with single mounting screw
Actuator rating
4 N•m (35 lb•in) minimum shaft length = 44 mm (1-3/4 in)
Damper shaft size
requirements
Round shaft diameter: 10 mm (3/8 in.) to 13 mm (1/2 in.)
Square shaft size: 10 mm (3/8 in.)
Serrated actuator coupling for additional grip.
Dimensions (H x W x D)
165 mm x 125 mm x 73 mm (6.5 in. x 4.92 in. x 2.9 in.)
Differential pressure
transducer (BYP200 only)
Range: -1.5 in. W.C. to 1.5 in. W.C.
Performance characteristics: Accuracy ±1.3% Full Span Maximum (± 039 in. W.C.)
Typical accuracy at zero (null) pressure is ±-.02% full scale
Shipping weight
0.65 kg (1.45 lb)
United States:
UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Compliance
Canada:
UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada Compliant, ICES-003
Table 19: ZEC510 VAV Controller
Specification
Description
Product code numbers
LC-ZEC510-x
Power supply requirement
20 VAC to 30 VAC at 50 Hz to 60 Hz, Class 2 power supply or Safety Extra-Low Voltage
(SELV) at 50/60 Hz (20 VAC minimum)
Power consumption
10 VA not including external load
Ambient conditions
Ambient operating conditions:
0°C to 50°C (32°F to 122°F); 10% to 90% RH condensing
Ambient storage conditions:
-40°C to 85°C (-40°F to 185°F); 10% to 90% RH
Processor
RX630 Renesas
®
32-bit microcontroller
Memory
1.5 MB flash nonvolatile memory for operating system, configuration data, and
operations data storage and 512k Synchronous Random Access Memory (SRAM) for
operations data dynamic memory
Mounting
On a flat surface with screws
Actuator rating
4 N•m (35 lb•in) minimum shaft length = 44 mm (1-3/4 in)
Damper shaft size requirements
Round shaft diameter: 10 mm (3/8 in.) to 13 mm (1/2 in.)
Square shaft size: 10 mm (3/8 in.)
Serrated actuator coupling for additional grip.
23