background image

Table 22: LC-VAC100x-0

Specification

Description

Product code numbers

LC-VAC100x-0 Verasys 18 point 24 V Application Controller with display

Supply voltage

24 VAC, 20 VAC minimum and 30 VAC maximum, 50/60 Hz, power supply class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)

Power consumption

20 VA maximum for LC-VAC100x-0

Note: 

VA rating does not include any power supplied to the peripheral devices

connected to Binary Outputs (BOs) or Configurable Outputs (COs). This can

consume up to 12 VA for each BO or CO; for a possible total consumption of an

additional 60 VA maximum.

Ambient conditions

Operating: 

-4°F to 158°F (-20°C to 70°C); 10% to 95% Relative Humidity (RH)

noncondensing; Pollution degree 2

Storage: 

-40°F to 185°F (-40°C to 85°C); 5% to 95% RH noncondensing.

Addressing

BACnet

®

 MS/TP: 

Valid field controller device addresses 4–127

Device addresses 0–3 and 128–255 are reserved and not valid field controller addresses.

N2: 

Valid field controller device addresses 1 to 255.

Communications bus

BACnet

®

 MS/TP, Modbus and N2 through RS-485:

3-wire System Bus between the supervisory controller and field controller

4-wire Sensor Bus between controller, network sensors and other sensor and

actuator devices, includes a lead to source 15 VDC supply power from controller to

bus devices

3-wire one modbus communication half-duplex, master RTU port.

Processor

RX631 Renesas

®

 32-bit microcontroller

Memory

16 MB flash memory and 8 MB RAM

Input and output capabilities

Five universal inputs: 

application-specific, three available modes (see application note

for wiring diagrams and usage):

Voltage input: 0 VDC to 10 VDC

Current sense input: 4 mA to 20 mA

Resistive inputs/dry contact inputs

Four binary inputs: 

Defined as dry contact maintained

Three configurable outputs: 

application-specific, two available modes:

Analog output: 0 VDC to 10 VDC, 10 mA

Triac output: 24 VAC, 0.5 A, externally sourced powered

One utility output power port (24~ OUT): 

Ability to deliver 24 VAC

Four binary outputs (relays): 

Single-pole, single-throw. Dry contacts rated 240 VAC.

UL: 240 VAC 5 A resistive, 1.9 LA/11.1LRA, D300 pilot duty, 70°C/158°F (30,000

cycles)

IEC: 240 VAC 3 A resistive, 3A inductive, Cos=0.6, -4°F to 158°F (-20°C to 70°C)

(100,000 cycles)

Note: 

Reference all relay commons to the same pole of the supply circuit.

Two BO Triacs: 

Output: 24 VAC or 240 VAC, 0.5 A, externally powered

Note: 

Reference all triac commons to the same pole of the supply circuit.

Analog input/Analog output

resolution and accuracy

Analog input:

 12-bit resolution

Analog output

: 15-bit resolution; +/- 200 mV accuracy in 0 VDC to 10 VDC applications

Terminations

Input and output: Fixed spade terminals
Sensor, system and modbus: 4-wire and 3-wire pluggable screw terminal blocks
Sensor Bus tool port: RJ-12 6-pin modular jack

Mounting

Horizontal on a single 35 mm DIN rail mount is preferred, or screw mount on flat surface

with three integral mounting clips on the controller
Mount the controller on a wall or DIN rail inside an enclosure rated at least IP20.

Housing

Enclosure material: Polycarbonate Lexan SABIC EXL9330

Dimensions (H x W x D)

6.45 in. x 4.92 in. x 2.08 in. (164 mm x 125 mm x 53 mm) excluding terminals and

mounting clips

Verasys System Product Bulletin

26

Summary of Contents for LC-BYP200-0

Page 1: ...C ZEC510 0 LC ZEC310 0 LC BYP200 0 LC VAC1000 0 LC VAC1001 0 LC VAC1002 0 LC VAC1100 0 LC VAC3000 0 LC IOM3711 0 Building Technologies Solutions www johnsoncontrols com 2021 04 08 Verasys System Produ...

Page 2: ...2 Verasys System Product Bulletin...

Page 3: ...features 12 Constant Volume application 12 Sideloop application 12 Verasys Zone Coordinator 12 TEC30xx or TEC36xx Thermostat controllers 12 Verasys Pro Wireless Field Bus System 13 Ideal applications...

Page 4: ...4 Verasys System Product Bulletin...

Page 5: ...sensors and damper assemblies All devices self configure and the Verasys Smart Building Hub SBH monitors the devices Through the SBH you can access the system using either a laptop smart phone or tab...

Page 6: ...ctivity Verasys Enterprise is a cloud based solution that provides a multi site aggregation of equipment data alarms setpoints and schedules to authorized users The enterprise application provides a h...

Page 7: ...users Verasys Tenant User Guide LIT 12013613 Using the SBH to configure the Verasys system Verasys System User s Guide LIT 12012371 Overview of Verasys system components features and operating modes...

Page 8: ...72 Verasys Input Output Module IOM Installation Guide Part No 24 10143 1256 Verasys ZEC510 VAV Controllers Installation Guide Part No 24 10143 01485 Verasys 18 Point 240 VAC Application Controller Ins...

Page 9: ...ume Controller Application Note LIT 12013067 Verasys Input Output Module Application Note LC VAC1002 0 LIT 12012992 Verasys Lighting Controller Application Note LIT 12012524 Verasys Sideloop Controlle...

Page 10: ...zone or bypass damper assembly when they are shipped The Zone and Bypass Damper controllers include advanced operating modes and multiple features that ensure occupant comfort A carbon dioxide CO2 dem...

Page 11: ...ghting controller VAC1001 The Verasys Lighting controller VAC1001 is a Verasys Application controller that controls up to nine lighting contactors that are grouped in zones You can control and schedul...

Page 12: ...rol a mixed air damper or set a minimum outside air damper position and meet Title 24 compliance for the state of California Other supported features include occupancy scheduling outdoor air lockouts...

Page 13: ...ficult or aesthetically unappealing to hardwire between products Examples of these locations include the following Office buildings university campuses educational facilities and other commercial stru...

Page 14: ...ntroller to the system bus its data automatically fills a predefined set of views based on the object type You can create profiles for third party controllers Profiles provide the following benefits Y...

Page 15: ...mizer Yes Yes Yes Yes Title 24 economizer Note 24 sequence and alarm notification is implemented from within the application State of California certification is pending Yes No Yes Yes Demand ventilat...

Page 16: ...ed cooling application Other applications are available For application files and documentation visit http verasyscontrols com LC ZEC510 0 Configurable VAV Box Controller all fan types staged incremen...

Page 17: ...SBH Manufacturer Model Name D LINK DWA 131 E D LINK DWA 171 A D LINK DWA 171 C NETGEAR A6100 TP LINK Archer PREMIERTEK PT 8811AU Table 9 Zone controller accessories Product code number Description Zo...

Page 18: ...fan coil and zoning No Yes Yes White TEC3012 16 000 On off or floating fan coil and zoning No Yes No White TEC3013 14 000 On off or floating fan coil and zoning Yes Yes Yes White TEC3022 13 000 0 to...

Page 19: ...Yes White TEC3622 16 000 0 to 10 VDC proportional fan coil and zoning No Yes No White TEC3623 14 000 0 to 10 VDC proportional fan coil and zoning Yes Yes Yes White TEC3630 13 000 Single or two stage...

Page 20: ...ZFR1821 Note Use the ZFR1821 EMT mount repeater for above the ceiling mounting Use the alternative ZFR1822 Pro Router for flush wall mount or below the ceiling mount applications Use a field provided...

Page 21: ...Two SA FC ports RJ12 6 pin port connects with 1 5 m 4 9 ft RJ 12 field bus cable and one screw terminal plug 4 pin Three USB ports one Micro B port and two USB A ports All support USB 2 0 and Open Hos...

Page 22: ...C in 0 5 increments Heating control 40 0 F 4 5 C to 90 0 F 32 0 C Temperature range Cooling control 54 0 F 12 0 C to 100 0 F 38 0 C Temperature 0 9F 0 5C at 70 0 F 21 0 C typical calibrated Accuracy H...

Page 23: ...1 2 in Square shaft size 10 mm 3 8 in Serrated actuator coupling for additional grip Dimensions H x W x D 165 mm x 125 mm x 73 mm 6 5 in x 4 92 in x 2 9 in Differential pressure transducer BYP200 onl...

Page 24: ...vice addresses 1 to 255 Communications bus BACnet MS TP 3 wire zone bus between the supervisory controller and the field controller 3 wire sensor bus between the controller network sensors and other s...

Page 25: ...ly mounted control suitable for DIN rain mounting Intended to mount in remote panel Type 1 C Micro interruption 330 V rated impulse voltage 125 C ball pressure test Australia and New Zealand RCM Mark...

Page 26: ...ic three available modes see application note for wiring diagrams and usage Voltage input 0 VDC to 10 VDC Current sense input 4 mA to 20 mA Resistive inputs dry contact inputs Four binary inputs Defin...

Page 27: ...ly Class 1 North America SELV Europe Power consumption 20 VA maximum for LC VAC110x 0 Note VA rating does not include any power supplied to the peripheral devices connected to BOs or COs This can cons...

Page 28: ...put output Fixed spade terminals Sensor system and modbus 4 wire and 3 wire pluggable screw terminal blocks Sensor Bus tool port RJ 12 6 pin modular jack Mounting Horizontal on a single 35 mm DIN rail...

Page 29: ...ble modes see application note for wiring diagrams and usage Voltage input 0 VDC to 10 VDC Current sense input 4 mA to 20 mA Resistive inputs and dry contact inputs 12 Binary Inputs Defined as dry con...

Page 30: ...60 Hz class 2 Transformer allowance 2 5 VA maximum 2 VA typical Provided through the three position 24 V screw terminal pluggable block 15 VDC 180 mA 7 VDC to 18 VDC 185 maximum current draw on the FC...

Page 31: ...less Field Bus Router wall mount for Field Controller Router Applications LC ZFR1821 0B Wireless Field Bus Router conduit mount with 24 VAC Power Supply for Field Controller Router Applications LC ZFR...

Page 32: ...n emissions compliance United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to p...

Page 33: ...tware terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open source...

Page 34: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice...

Reviews: