Programming Manual
GLASSFRONT VENDING MACHINES
Rev. 1.12
MODELLS: G-DRINK SVE GF6 / GF9 – DR6 / DR9
Page 41 of 42
4.2 ELECTRONIC COOLING UNIT CONTROL CAREL USED FROM MARCH 2010
Display
Key board
Key 1 UP, in normal function if pushed for more than
1 second, it visualizes the temperature of probe 2
(evaporator). If pushed during the visualization of the
set point it increases the set value.
Key 2 pushed more that 1 second allows the
visualization and setting of the set point.
Key 3 DOWN, pushed for more than 3 seconds
starts or stops the defrost, and if it is pushed during
the visualization of the set point it decreases the set
value.
To check and adjust the temperature.
•
Push for more than 1 second SET, to visualize the temperature of the set point;
•
Increase or decrease the value with UP or DOWN;
•
Push SET to confirm the new value.
Description and function of the CAREL Electronic cooling unit control.
When switching on the control unit for the first times there will be a delay of three minutes
in the compressor and evaporator fan starting .
During normal working, the compressor will stop only after reaching the set point
temperature and the evaporator fans will work always.
When opening the door (if there is a door switch) both the compressor (if working) and
fans will stop.
When closing the door, the fans will start immediately, while the compressor will have a
delay of three minutes from the last switching off, even if the door is closed before.
1. Compressor led
2. Fan led
3. Defrost led
4. Auxiliary exit
5. Clock
6. Alarm
7. 7-LED Segment