6 Set up with the indicating and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
Since the scaling is very extensive, the scaling of the interface meas-
ured value was divided into two menu items.
In menu item "
Interface 2
" you define the scaling format on the display
and the scaling of the interface measured value for 0 % and 100 %.
In menu item"
Current output, size
" you determine which measured
value the current output refers to.
In menu item "
Current output, adjustment
" you can assign a respec-
tive measured value to the current output.
In the menu item "
Current output Min./Max.
", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
Setup/Scaling - Interface
2
Setup/Current output -
Size
Setup/Current output -
Adjustment
Setup/Current output
Min./Max.