6 Set up with the indicating and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
Menu
Menu item
Default value
Setup
Lock operation
Released
Measurement
loop name
Sensor
Units
Distance unit: mm
Temperature unit: °C
Probe length
Length of the probe Ex factory
Product type
Liquid
Applications
Level, vessel
Medium, dielectric
constant
Water-based, > 10
Max. adjustment
0.000 m(d) - note blocking distances
Min. adjustment
Probe length - take dead band into
account
Linearisation
Linear
Damping
0.0 s
Scaling size
Volume in l
Current output -
adjustment
0.00 lin %, 0 l
100.00 lin %, 100 l
Current output -
mode
Last measured value
Current output -
Min./Max.
Min. current 3.8 mA, max. current
20.5 mA
Display
Language
As set in the device
Displayed value 1 Filling height, level
Displayed value 2 Electronics temperature
Backlight
Switched off
Additional adjust-
ments
PIN
0000
Probe type
Like order
HART mode
Address 0 - Standard
The instrument settings are copied with this function. The following
functions are available:
•
read from sensor: Read data from sensor and store into the indi-
cating and adjustment module
•
write into sensor: Store data from the indicating and adjustment
module back to the sensor
The following data or settings for adjustment of the indicating and
adjustment module are saved:
•
All data of the menu "
Setup
" and "
Display
"
•
In the menu "
Additional adjustments
" the items "
Reset, Date/Time
"
•
Special parameters
Additional adjustments/
Copy instrument settings