![Vega vegaflex 83 Operating Instructions Manual Download Page 31](http://html2.mh-extra.com/html/vega/vegaflex-83/vegaflex-83_operating-instructions-manual_3941722031.webp)
31
6 Set up with the indicating and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
In this menu item you can enter the min. adjustment for the level. This
is the min. total level with interface measurement.
Adjust the requested percentage value with
[+]
and save with
[OK]
.
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the flange to the probe end) corresponding to the per-
centage value. The distance refers tot he sensor reference plane (seal
surface of the process fitting).
This menu item is only available if you have selected interface meas-
urement under the menu item "
Application
".
You can accept the adjustment of the level measurement also for the
interface measurement. If you select "Yes", the actual setting will be
displayed.
If you have selected "
No
", then you can enter the adjustment for the
interface separately. Enter the requested percentage value.
Enter the distance value in m for the full vessel suitable for the per-
centage value.
This menu item is only available if you have selected interface meas-
urement under the menu item "
Application
". If you have selected "
Yes
"
in the previous menu item (accept adjustment of the level measure-
ment), then the actual setting will be displayed.
Setup/Min. adjustment -
Level
Setup/Max. adjustment -
Interface
Setup/Min. adjustment -
Interface