9 Diagnostics and service
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
Code
Text mes-
sage
Cause
Rectification
F261
Error in the
instrument
settings
– Error during setup
– Error when carrying out a
reset
– False signal suppression
faulty
– Carry out a reset
– Repeat setup
F264
Installation/
Setup error
– Error during setup
– Check or correct installation
and/or parameter adjust-
ment
– Check probe length
F265
Measurement
function dis-
turbed
– Sensor no longer carries
out a measurement
– Carry out a reset
– Separate operating voltage
briefly
F266
Incorrect sup-
ply voltage
– Terminal voltage below
specified range
– Check electrical connection
– if necessary, increase
operating voltage
The following table shows the error codes and text messages in the
status message "
Function check
" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
C700
Simulation ac-
tive
– A simulation is active
– Finish simulation
– Wait for the automatic end
after 60 mins.
The following table shows the error codes and text messages in the
status message "
Out of specification
" and provides information on
causes as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
S600
Unpermissi-
ble electronics
temperature
– Temperature of the elec-
tronics in the non-specified
section
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
S601
Overfilling
– Danger of vessel overfilling
– Make sure that there is no
further filling
– Check level in the vessel
The following table shows the error codes and text messages in the
status message "
Maintenance
" and provides information on causes
as well as corrective measures.
Function check
Out of specification
Maintenance