6 Set up with the indicating and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
In this menu item you can select which type of medium you want to
measure. You can choose between liquid or bulk solid.
In this menu item, you can select the application. You can choose
between level measurement and interface measurement. You can
also choose between measurement in the vessel or in the bypass or
standpipe.
Note:
The selection of the application has a considerable influence on all
other menu items. Keep in mind that as you continue with the param-
eter adjustment, individual menu items are only optionally available.
You have the possibility to choose the demonstration mode.This
mode is suitable for test and demonstration purposes. In this mode,
the sensor ignores the logic parameters of the application and reacts
immediately to each change.
You have to enter the tube inner diameter when measuring in a
bypass or standpipe.
In this menu item, you can define the medium type (product).
This menu item is only available if you have selected level measure-
ment under the menu item "
Application
".
You can choose between the following medium types:
Dielectric con-
stant
Product type
Examples
≥ 10
Water-based liq-
uids
Acids, alcalis, water
> 3 … < 10
Chemical mix-
tures
Chlorobenzene, nitro lacquer, aniline,
isocyanate, chloroform
≤ 3
Hydrocarbons
Solvents, oils, liquid gas
Setup/Medium type
Setup/Application
Setup/Medium, dielectric
constant