Alarm Index and Corrective Action
6
Alarm Index and Corrective Action
Table 1 lists each alarm, a possible cause, and a suggested corrective action.
Table 1. Alarm Index, Cause, and Corrective Action
Alarm
Cause
Action
PROBE OUT
Hardware failure - probe
inoperative, or its intercon-
necting wiring to console is
damaged.
Call for service following the procedures
established for your site.
INVALID HEIGHT
Product level too low, caus-
ing the fuel and water floats
to be too close together.
Call for delivery.
LOW TEMPERATURE
Probe temperature drops
below -4°F (-19.8°C).
Probe returns to normal operation after
probe temperature rises above -4°F
(-19.8°C).
NO TANKS CONFIGURED
No tanks are configured in
Tank Setup.
Configure at least one tank in Tank Setup.
MAX PRODUCT
Product volume increased
beyond preset limit.
Stop delivery. Do not allow additional deliv-
ery until product volume decreases below
preset limit.
OVERFILL
Product volume increased
beyond preset limit.
Stop delivery. Check for spillage.
LOW PRODUCT
Product volume decreased
below preset limit.
Call for delivery.
HIGH WATER
Water level rose above pre-
set limit.
Remove water from tank.
Summary of Contents for TLS-50 Series
Page 1: ...Manual No 577013 609 Revision F Setup and Operation TLS 50 Console...
Page 24: ...i SPANISH...
Page 47: ...i FRENCH...
Page 70: ...i CHINESE...
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ...27 PORTUGUESE...
Page 116: ...For technical support sales or other assistance please visit www veeder com...