TLS-50 Setup
Tank Setup
11
Figure 7. Tank Setup Menu
consoles\tls50\50tkst1.eps
T1: THERMAL COEFF
0.00000
T1: DIAMETER
0000.0 MM
T1: CONFIGURED
YES
T1: PROFILE
1 PT
T1: FULL VOLUME
000000 LIT
T1: XXXX.X MM VOL
000000 LIT
TANK SETUP
PRESS
Set this entry to YES for each tank that has a probe installed.
To ensure proper calculation of TC volume, you must enter the Coefficient of Thermal Expansion for the fuel in
each tank. The following table lists the U.S. and Metric (M) thermal coefficients for approved fuels and liquids:
PRODUCT
TC (U.S.)
TC (M)
Enter the inside diameter of the selected tank (for a linear tank, the tank height = tank diameter). You can find this
dimension on the Tank Chart. Range: 0.00 to 144.00 inches (0.0 to 3657.6 mm).
Use this display to select the number of height/volume values you wish to enter for the tank. Options are 1, 4, or
Linear. The system will use these values, along with the Tank Diameter, to calculate volume readings at heights
along the entire length of the probe. Use the following guidelines to enter the Tank Profile:
- Steel (flat-ended) tank - 1 point
- Fiberglass tank - 4 points
- Cylindrical tank standing on end - Linear
- Rectangular tank - Linear
- Fiberglass tank - 20 points
T1: XXXX.X MM VOL
000000 LIT
All tanks must have the volume at 100% diameter entered. If you entered 1 Point or Linear for Tank Profile above,
the next display will be the Tilt entry. If you entered 4 points or 20 points for Tank Profile you will have to enter the
full volume (this entry) and in addition, volumes for each of the remaining points (3 or 19) depending on which
profile you selected. Each of the heights (points) have been calculated by the TLS-50. As you step through the
points (3 or 19), you enter the volume from the tank chart for the displayed height. Range: 0 - 260,000 gallons (0 -
984,000 litres). NOTE: if 4 or 20 point profiles are selected and all points are not entered, the volume will compute
to zero.
If you selected 4 or 20 points in the Profile display above, you must enter the volume at the
level of the tank shown in the top line of this display. Enter the volume at this height from
the tank chart. Range for each point: 0 - 260,000 gallons (0 - 984,000 litres).
T1: TILT;
+0000.0 MM
Fuel Oil #4
Gear Oil,90W
Hydraulic Oil
Transmission Fluid
Turbine Oil
Ethylene Glycol
Water
Washer Fluid
Used Oil
0.00085
0.00085
0.00085
0.00085
0.00085
0.00067
0.00022
0.00085
0.00079
PRODUCT
TC (U.S.)
TC (M)
Aviation Gas
Regular Unleaded
Premium
Leaded
Gasohol
Jet Fuel
Kerosene (fuel oil #1)
Diesel (fuel oil #2)
Motor Oil
Alcohol
0.00135
0.00126
0.00126
0.00126
0.00125
0.00085
0.00090
0.00081
0.00085
0.00114
0.00075
0.00070
0.00070
0.00070
0.00069
0.00047
0.00050
0.00045
0.00047
0.00063
0.00047
0.00047
0.00047
0.00047
0.00047
0.00077
0.00012
0.00047
0.00044
Continued on next page.
4 or 20
point
profile
Tank or
Linear
profile
OR
Continue to enter the volumes for each of the remaining points.
Summary of Contents for TLS-50 Series
Page 1: ...Manual No 577013 609 Revision F Setup and Operation TLS 50 Console...
Page 24: ...i SPANISH...
Page 47: ...i FRENCH...
Page 70: ...i CHINESE...
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ...27 PORTUGUESE...
Page 116: ...For technical support sales or other assistance please visit www veeder com...