Installation
Fuel Conditioner (FC) Installation
17
STP Adapter Assembly Installation - FE Petro STP
Turn off the electricity, tag and lockout the electrical power switch to the
dispenser/pump. Relieve pump pressure before proceeding with this
installation.
4. Get the STP Adapter Assembly
from the kit (see Figure
Figure 15. FE Petro STP Adapter Assembly
5. Remove the 3/8” NPT siphon port plug from the STP (see Figure
13).
Figure 16. Locating FE Petro Siphon Port
6. Apply a coat of fresh, UL classified for petroleum, non-setting thread sealant.to the threads of the STP Adapter
Assembly and install it in the siphon port and tighten securely.