TCI-W11-U, TCI-W22-U Universal Controller 

D

ISPLAY AND 

O

PERATION

 

 

Doc: 70-00-0140C, V2.0-20220523  

© Vector Controls LLC, USA  

Page 6-24 

Subject to alteration 

Operating Mode 

Display 

Description 

 

Occupied (Comfort) 

-

 

All control functions operating per set points 

 

Unoccupied (Economy) 

-

 

Set points shifted according to 1L07, 2L07 

OFF 

Protection (Energy Hold Off) 

-

 

Outputs are off, inputs monitored for alarms 

 

Controlling Mode 

Display 

Description 

 

Cooling 

-

 

Cooling (Direct) Active 

 

Heating 

-

 

Heating (Reverse) Active 

 

Manual 

-

 

Manual Override 

 

Clock / Schedules 

-

 

Schedule Set 

 

Fan 

-

 

Fan Active 

 

Operation Status 

Display 

Description 

 

Alarm 

-

 

Alarm active 

 

Standard display (Parameters UP08, UP09, UP10) 

 

Active when no key has been pressed for 30 seconds. 

 

Contents may be chosen with parameters.  

Loop display 

 

Active when changing set points.  

 

Large digits show input value if 1L 27 or 2L 27 = OFF. Small digits show set point.  

If 1L 27 or 2L 27 = ON, only the setpoint is shown in the large digits.  

 

Vertical bars show analog output value. Arrows in position 1, 2 and/or 3 show active binary (digital) output stages 

Display in OFF mode 

 

When the device is switched off, all enabled input values and the clock are displayed each for 4 seconds on the large LCD 

digits in a continuous cycle while OFF is displayed in the small digits. To prevent this, make sure that in idle mode no 

input values are shown on either small or large digits by setting UP09 and UP11 to something else than 1.  

Override of secondary set point in cascade control 

 

If cascade control is active, with variable air volume (VAV) for example, the user can override the primary loop and 

manually select the set point of the secondary loop-the loop is now changed to constant air volume (CAV). Typically for 

tuning the VAV system. This feature may be disabled with UP02.  

 

While the secondary loop is displayed change the set point with UP/DOWN 



. Override Cascade symbol appears. 

 

Press OPTION to move back to the temperature loop and cancel cascade override.  

Power Failure 

 

All parameters and set points are automatically saved and do not need to be re-entered.  

 

Upon return of power: Set 

Parameter UP05 

to keep the unit off, switch on, or operation mode before power failure. 

 

Clock and time schedule settings retained for 48 hours (after powered for at least 10 hours). 

Alarm messages 

Small Digit 

LCD Symbol 

Alarm Condition 

ALA1 

 

ALA8 

 

Alarm for low/high input or output limits according to configuration. 

 

 

For details on configuring alarms see input configuration on page 11, output configuration on page 15, or 

auxiliary function on page 20. 

 

 

 

Summary of Contents for 40-10 0265

Page 1: ...oops 8 time schedules 1 internal temperature sensor 2 universal inputs 2 binary PWM outputs 1 analog output Internal temperature sensor standard Add replaceable humidity element as required AES3 HT A2...

Page 2: ...tability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 250 Re...

Page 3: ...24VAC 24VDC DO Binary outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper AO Analog output 0 10 V or 0 20 mA...

Page 4: ...er heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less c...

Page 5: ...OFF displayed with current time W22 temperature W11 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W22 SCHEDULES TC...

Page 6: ...ch for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or large...

Page 7: ...ayed For TCI W22 Press OPTION 2 sec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W11 Press OPTION 2 sec S...

Page 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Page 9: ...configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneously...

Page 10: ...UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3 1U...

Page 11: ...pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of 50 205 may be adjusted with multipliers inU03 The largest...

Page 12: ...setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling Un...

Page 13: ...hat the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals th...

Page 14: ...ngeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2 is...

Page 15: ...define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog control sequence is not active until...

Page 16: ...ing mode decreases airflow dwindles until it reaches minimum cooling output 1A05 This minimum will be based on the airflow needed at design cooling and is typically 10 to 15 of maximum cooling airflow...

Page 17: ...demand active before output on In state mode 1d01 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0 act...

Page 18: ...s With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be...

Page 19: ...larms are defined with input parameters With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be sig...

Page 20: ...275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an outdoor t...

Page 21: ...imit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Page 22: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Page 23: ...TCI W11 U TCI W22 U Universal Controller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 23 24 Subject to alteration Empty page...

Page 24: ...roller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 24 24 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls LLC USA infous vectorc...

Reviews: