background image

 

TCI-W11-U, TCI-W22-U Universal Controller 

T

ECHNICAL 

S

PECIFICATION

 

 

Doc: 70-00-0140C, V2.0-20220523  

© Vector Controls LLC, USA  

Page 2-24 

Subject to alteration 

Technical specifications 

 

WARNING! 

This device is intended to be used for comfort applications. Where a device failure endangers human life and/or 

property, it is the responsibility of the owner, designer and installer to add additional safety devices to prevent or 

detect a system failure caused by such a device failure. The manufacturer of this device cannot be held liable for 

any damage caused by such a failure.  

Ignoring specifications and local regulations may endanger life, cause equipment damage and void warranty. 

 

Power Supply 

Power Requirements  

24 VAC ±10%, 50/60 Hz, Class 2, 2.0 A, 48 VA max. 
24 VDC ±10%

 

 

Power Consumption 

Max. 3 VA 

 

Electrical Connection 

Terminal Connectors 

0.34…2.5 mm

2

 

wire (AWG 24…12)

 

 

Clock backup 

Min. 48 hours 

Signal inputs 

Universal Input 
Input Signal 

Resolution 
Impedance 

Setting for Voltage or Current 
0

10 V or 0

20 mA 

9.76 mV or 0.019 mA (10 bit) 

Voltage: 98kΩ

 

Current: 240Ω

 

 

Universal Input 
Range 
Accuracy 

Input configured to remote temperature (RT) or digital input (DI) 
NTC (Sxx-Tn10 sensor): -

40…140 

°C (-

40…284 °F)

 

-

40…0 °C (

-

40…32 °F): 0.5 K

 

0…50 °C (32…122 °F): 0.2 K

 

50…100 °C (122…212 °F): 0.5 K

 

> 100 °C (> 212 °F): 1 K 

Humidity Sensor AES3-HT-Ax: 
Range 
Measuring Accuracy 
Hysteresis 
Repeatability 
Stability 

Capacity sensor  

0…100 % rH

 

See Figure to the right 

 1% 

 0.1% 

< 0.5% / year 

 

Signal outputs 

Analog Output 
Output Signal 
Resolution 
Maximum Load 

 
DC 0

10 V / 0

20 mA 

9.76 mV / 0.019 mA 
Voltage: 

1kΩ

 

Current: 

250

 

 

Relays Outputs 
AC Voltage 
DC Voltage 

 

0…

48 VAC, 2(1.2)A max. (Observe local regulation)  

0…30 VDC, 2A max. 

 

 

Insulation strength 
between relays contacts and system 
electronics: 
between neighboring contacts: 

 
 
2000V AC to EN 60 730-1 
1250V AC to EN 60 730-1 

Environment 

Operation 
Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 

0…50 °C (32…122 °F)

 

<95 % RH non-condensing 

 

Transport & Storage 
Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25

…7

0 °C (-13

…158 

°F) 

<95 % RH non-condensing 
class 2M2 

Standards 

Degree of Protection 

IP30 to EN 60 529 

 

Pollution Class 

II (EN 60 730-1) 

 

Safety Class 

III (IEC 60536) 

 

Overvoltage Category 

I (EN 60 730-1) 

General 

Material:  

Cover, back part 

 

Mounting Plate 

Fire proof ABS plastic (UL94 class V-0) 
Aluminum 

 

Dimension (H x W x D) 

Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.) 

Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)

 

 

Weight (including package) 
TCI-W11-U 
TCI-W22-U 

 
205g (7.2 oz.) 
220g (7.8 oz) 

 

Product testing and certification 

 

Declaration of conformity 

Information about the conformity of our products can be found on our website 

www.vectorcontrols.com on the corresponding product page under "Downloads" 

Figure 1: Max RH-tolerance at 25°C (77°F) 

per sensor type 

Relative humidity accuracy 

 %RH 

 %RH 

10  20  30  40 

100 

90 

50  60  70  80 

±1 
±0 

±2 

±3 

±4 

±5 

AES3-HT-A2 

AES3-HT-A3 

AES3-HT-A5 

Summary of Contents for 40-10 0265

Page 1: ...oops 8 time schedules 1 internal temperature sensor 2 universal inputs 2 binary PWM outputs 1 analog output Internal temperature sensor standard Add replaceable humidity element as required AES3 HT A2...

Page 2: ...tability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 250 Re...

Page 3: ...24VAC 24VDC DO Binary outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper AO Analog output 0 10 V or 0 20 mA...

Page 4: ...er heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less c...

Page 5: ...OFF displayed with current time W22 temperature W11 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W22 SCHEDULES TC...

Page 6: ...ch for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or large...

Page 7: ...ayed For TCI W22 Press OPTION 2 sec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W11 Press OPTION 2 sec S...

Page 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Page 9: ...configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneously...

Page 10: ...UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3 1U...

Page 11: ...pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of 50 205 may be adjusted with multipliers inU03 The largest...

Page 12: ...setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling Un...

Page 13: ...hat the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals th...

Page 14: ...ngeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2 is...

Page 15: ...define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog control sequence is not active until...

Page 16: ...ing mode decreases airflow dwindles until it reaches minimum cooling output 1A05 This minimum will be based on the airflow needed at design cooling and is typically 10 to 15 of maximum cooling airflow...

Page 17: ...demand active before output on In state mode 1d01 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0 act...

Page 18: ...s With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be...

Page 19: ...larms are defined with input parameters With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be sig...

Page 20: ...275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an outdoor t...

Page 21: ...imit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Page 22: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Page 23: ...TCI W11 U TCI W22 U Universal Controller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 23 24 Subject to alteration Empty page...

Page 24: ...roller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 24 24 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls LLC USA infous vectorc...

Reviews: