background image

 

TCI-W11-U, TCI-W22-U Universal Controller 

C

ONTROL LOOP 

C

ONFIGURATION

 

 

Doc: 70-00-0140C, V2.0-20220523  

© Vector Controls LLC, USA  

Page 12-24 

Subject to alteration 

Control loop configuration 

Manipulation of the setpoint (1L and 2L) 

Parameter 

Description 

Range 

Default 

1L 00 

Select loop control input (0= loop disabled): 

1= 1T,  2= 1H,  3= 1U,  4= 2U 

0

1L 01 

Minimum set point limit heating 

per input 

10°C (50°F) 

1L 02 

Maximum set point limit heating 

per input 

28°C (82°F) 

1L 03 

Minimum set point limit cooling 

per input 

18°C (64°F) 

1L 04 

Maximum set point limit cooling 

per input 

34°C (93°F) 

1L 05 

Enable set point compensation (0= disabled) 

1= winter compensation,  2= summer compensation,  3= winter and summer 

0

1L 06 

Loop input special (0= normal): 

1= combine loop 1 and loop 2   

2= cascade with reverse sequence of primary loop 

3= cascade with direct sequence primary loop 

4= cascade with both reverse and direct sequence of primary loop  

0

1L 07 

Unoccupied (economy) mode set point shift: (Function depends on 1L25) 

The occupied (comfort) setpoint is shifted by the value set with parameter. 

Reduces the heating set point and increases the cooling set point.  

per input 

5.0°C(10°F) 

1L 08 

Dead zone between heating and cooling set points 

The Dead Zone Span lies between the heating and the cooling setpoint. The 

output is off while the measured value is within the dead zone span. A negative 

dead zone is not possible. 

Per input 

1.0°C (2°F) 

1L 25 

Fixed setpoint in Unoccupied (ECONOMY) mode  

OFF = Unoccupied (ECONOMY) set point shift applies 

ON = In Unoccupied (ECONOMY) mode use minimum setpoint limit as 

setpoint in heating mode or maximum setpoint limit in cooling mode 

ON, OFF 

OFF 

1L 26 

Setpoint compensation range, the maximum range the setpoint is shifted.  

0 = Temperature setback: the setpoint is shifted towards setpoint limit 

Acc input 

0.0°C 

1L 27 

Do not show current value in loop mode 

OFF = Current value is shown in loop mode in the large digits. The setpoint 

in the small ones.  

ON = Current value is not shown, the setpoint is shown in the large digits.  

ON, OFF 

OFF 

 

Unoccupied (economy) mode setpoints: There are two possibilities to change the setpoint in unoccupied (economy) 

mode: Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling.  

Unoccupied (economy) mode may be disabled by setting UP06 to OFF.  

 

Control loops and sequences are activated when output parameters are defined.  

 

Cascade control

 

In cascade control (L06) the setpoint of the secondary loop is determined by the demand of the primary loop. The 

setpoint of the secondary loop is calculated proportionally according to demand of the primary loop between minimum 

and maximum setpoint limits. Cascade control is activated by setting the parameter 

X

L06 of the secondary control loop. 

A typical application is a variable air volume system where the temperature output determines the pressure set point.  

Cascade Control Example 

 VAV Application 

Primary loop = temperature (1L) 

Secondary loop = airflow/pressure (2L) 

 

Settings: 2L01=20%,  2L02=60%,  2L06=2 

Depending on temperature setpoint, 

the demand is calculated for loop 1. 

For example 40%.  

Based on demand of loop 1, the setpoint of pressure loop is calculated 

proportionally between min (20%) and max (60%) pressure setpoint limits.  
A demand of 40% will result in a setpoint of 36% in the above example.  

 

Setpoint Compensation

 

The setpoint compensation is typically used to compensate the set point due to a change in outside temperature. The 

relationship to the input used to drive the setpoint compensation is defined in auxiliary functions FU00 to FU07. 

 

Enable summer or winter set point compensation for this control loop with L05. Define the compensation range with 

L26.L26 defines the full setpoint shift once the compensation input has reached its lower limit in winter mode or upper 

limit in summer mode. 

Setting the range parameter to 0 will activate the setpoint setback function: The setback function shifts the set point 

toward the set point minimum or the set point maximum based on an external input value. Once the compensation input 

has reached its lower limit in winter mode or upper limit in summer mode, the setpoint is fixed to the setpoint minimum 

or maximum value. Commonly this is used for humidity control to avoid condensation on outside walls or windows in very 

cold weather.  

 

 

Summary of Contents for 40-10 0265

Page 1: ...oops 8 time schedules 1 internal temperature sensor 2 universal inputs 2 binary PWM outputs 1 analog output Internal temperature sensor standard Add replaceable humidity element as required AES3 HT A2...

Page 2: ...tability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 250 Re...

Page 3: ...24VAC 24VDC DO Binary outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper AO Analog output 0 10 V or 0 20 mA...

Page 4: ...er heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less c...

Page 5: ...OFF displayed with current time W22 temperature W11 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W22 SCHEDULES TC...

Page 6: ...ch for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or large...

Page 7: ...ayed For TCI W22 Press OPTION 2 sec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W11 Press OPTION 2 sec S...

Page 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Page 9: ...configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneously...

Page 10: ...UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3 1U...

Page 11: ...pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of 50 205 may be adjusted with multipliers inU03 The largest...

Page 12: ...setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling Un...

Page 13: ...hat the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals th...

Page 14: ...ngeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2 is...

Page 15: ...define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog control sequence is not active until...

Page 16: ...ing mode decreases airflow dwindles until it reaches minimum cooling output 1A05 This minimum will be based on the airflow needed at design cooling and is typically 10 to 15 of maximum cooling airflow...

Page 17: ...demand active before output on In state mode 1d01 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0 act...

Page 18: ...s With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be...

Page 19: ...larms are defined with input parameters With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be sig...

Page 20: ...275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an outdoor t...

Page 21: ...imit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Page 22: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Page 23: ...TCI W11 U TCI W22 U Universal Controller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 23 24 Subject to alteration Empty page...

Page 24: ...roller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 24 24 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls LLC USA infous vectorc...

Reviews: