background image

 

TCI-W11-U, TCI-W22-U Universal Controller 

C

ONTROL LOOP 

C

ONFIGURATION

 

 

Doc: 70-00-0140C, V2.0-20220523  

© Vector Controls LLC, USA  

Page 13-24 

Subject to alteration 

PI control sequence 

Parameter 

Description 

Range 

Default 

1L 09 

Offset for heating PI sequence 

per input 

1L 10 

Offset for cooling PI sequence 

per input 

1L 11 

P-band heating  

per input 

2.0°C (4.0°F) 

1L 12 

P-band cooling  

per input 

2.0°C (4.0°F) 

1L 13 

Integral gain heating (0.1 steps) 

low= slow reaction, high= fast reaction 

0

25.5 

0.0 

1L 14 

Integral gain cooling (0.1 steps) 

0

25.5 

0.0 

1L 15 

Measuring interval integral (seconds) 
low= fast reaction, high value= slow reaction 

0

255 

1 sec. 

 

Proportional control(P-band) 

The proportional control function calculates the output based on the difference between setpoint and measured value. The 
proportional band (P-band) defines the difference between setpoint and measured value which will result in a 100% 

output. For example, with a heating or reverse 0-10 V control sequence, and a 2.0°C (4.0°F) P-band value, at 10 V the 
controller will be 2.0°C (4.0°F) below setpoint. This is the working range of the proportional control sequence. 

Setting the proportional band to 0 disables proportional control. 

 

 

Integral and Differential control 

Proportional control is in most cases a very stable control mode. The flaw of proportional control alone, however, is that 

the setpoint is normally not reached. As the measured value gets closer to the setpoint, the output reduces until it 

reaches a point, a fraction above or below the setpoint, where the output equals the load. To reach the setpoint and 

achieve a higher level in comfort the Integral/Differential function should be activated. 

Integral Gain (KI)

dynamically increases the output by the selected KI value every 

Measuring Interval TI

 until the 

setpoint is reached. The challenge is to prevent hunting, where the output increases too fast, the temperature overshoots 

the setpoint, the output goes to 0, the temperature undershoots the setpoint, and the cycle repeats itself. Hunting may 

result if the integral gain is too high or measuring interval too short. Each system is different. To prevent instability the P-

band should be extended when integral gain is active (L14 or L15 set above 0).  

Setting the integral gain to 0 disables integral and differential control. 

Recommended Values 

 

heating 

(air) 

heating 

(radiant) 

humidifying 

cooling 

dehumidifying 

pressure 

P-band 

2

3°C (4

6°F) 

1

1.5°C (2

3°F) 

Measuring interval (TI) 

15 

70 

Integral gain (KI) 

0.2 

0.1 

0.1 

0.2 

0.3 

0.8 

 

 

 

 

 

Heating/Reverse 

Cooling/Direct 

100 

T [°C, °F] 
U [V, mA] 

Y

H1

, Y

R1 

X

PH

 

W

X

PC

 

X

DZ

 

Y

C1, 

Y

D1

 

W

X

SBY

 

X

SBY

 

Legend 

T, U 

Input signal temp/universal 

X

PH

 

P-band heating/direct 

 

X

PC

 

P-band cooling/reverse 

 

X

DZ

 

Dead zone h/c set points 

X

SBY

 

Economy mode set point shift 

W

H

 

Set point heating/reverse  

W

C

 

Set point cooling/direct 

Y

H1, 

Y

R1

  PI sequence heating/reverse 

Y

C1, 

Y

D1

  PI sequence cooling/direct 

Summary of Contents for 40-10 0265

Page 1: ...oops 8 time schedules 1 internal temperature sensor 2 universal inputs 2 binary PWM outputs 1 analog output Internal temperature sensor standard Add replaceable humidity element as required AES3 HT A2...

Page 2: ...tability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 250 Re...

Page 3: ...24VAC 24VDC DO Binary outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper AO Analog output 0 10 V or 0 20 mA...

Page 4: ...er heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less c...

Page 5: ...OFF displayed with current time W22 temperature W11 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W22 SCHEDULES TC...

Page 6: ...ch for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or large...

Page 7: ...ayed For TCI W22 Press OPTION 2 sec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W11 Press OPTION 2 sec S...

Page 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Page 9: ...configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneously...

Page 10: ...UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3 1U...

Page 11: ...pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of 50 205 may be adjusted with multipliers inU03 The largest...

Page 12: ...setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling Un...

Page 13: ...hat the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals th...

Page 14: ...ngeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2 is...

Page 15: ...define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog control sequence is not active until...

Page 16: ...ing mode decreases airflow dwindles until it reaches minimum cooling output 1A05 This minimum will be based on the airflow needed at design cooling and is typically 10 to 15 of maximum cooling airflow...

Page 17: ...demand active before output on In state mode 1d01 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0 act...

Page 18: ...s With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be...

Page 19: ...larms are defined with input parameters With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be sig...

Page 20: ...275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an outdoor t...

Page 21: ...imit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Page 22: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Page 23: ...TCI W11 U TCI W22 U Universal Controller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 23 24 Subject to alteration Empty page...

Page 24: ...roller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 24 24 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls LLC USA infous vectorc...

Reviews: