VDH Products BV
Document 063319 - version 3.12
Page:
53 of 78
Number
Description
Range
Value
Default
1700
Temperature Alarms
1701
1702
1703
1704
1705
1706
1707
1708
1709
1710
1711
1712
1713
1714
1715
1716
1717
1718
1750
1751
1752
1760
1761
1762
Absolute maximum alarm 1
Absolute minimum alarm 1
Delay absolute alarm 1
Absolute maximum alarm 2
Absolute minimum alarm 2
Delay absolute alarm 2
Relative maximum alarm 1
Relative minimum alarm 1
Delay relative alarm 1
Relative maximum alarm 2
Relative minimum alarm 2
Delay relative alarm 2
Absolute maximum air temperature
Absolute minimum air temperature
Relative maximum air temperature
Relative minimum air temperature
Differential maximum air temperature
Differential minimum air temperature
Maximum RH alarm
Minimum RH alarm
RH alarms active
Maximum pressure alarm
Minimum pressure alarm
Pressure alarms active
-10..40.0
-10..40.0
0..999
-10..40.0
-10..40.0
0..999
0..10.0
-10..0.0
0..999
0..10.0
-10..0.0
0..999
-10..40.0
-10..40.0
0..10.0
-10..0.0
0.1..10.0
0.1..10.0
0..110
0..110
0..1
0..10.00
0..10.00
0..1
°C
°C
min
°C
°C
min
°C
°C
min
°C
°C
min
°C
°C
°C
°C
°C
°C
% RH
% RH
-
-
-
-
25.0
10.0
0
20.0
12.0
0
5.0
-5.0
30
1.0
-1.0
30
20.0
10.0
3.0
-3.0
0.5
0.5
100
0
0
10.00
0.00
0
Summary of Contents for PROBA