Installation, Operating & Maintenance Instructions
Series 650 DN 350 (I.D. 14”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
286241EA
2010-10-11
43/86
The «range of pressure and position values» is independent of the data type, equal for «signed integer» and «floating
point».
Note: The internal accuracy of valve is for all positions 100’000 steps and for all pressures 1’000’000 steps. If the range of
pressure and position values is rising, the accuracy of pressure and position will not rise. There is only the gain factor
between the VAT valve and the CC-Link Master which will be adapted.
Note:
(upper scale value - lower scale value)
≥
1
Note: If at startup the scale values in the memory are out of range or the rule above is broken the default values are
taken. In this case the get command i:24 add a string “False”:
Example: s:24031234.56to7890
Æ
set the range of position from 1234.56 (= closed position) to 7890 (= opened position)
Example: s:24000to100.75
Æ
set the range of pressure from 0 (= 0 V) to 100.75 (= 10 V)
Example: s:2407-10.5to20.5
Æ
set the range of Position setpoint from -10.5 (=closed position)
to 20.5 (=opened position)
6. Logic digital input close valve configuration
The «logic digital input close valve» can adjusted. See also chapter «LOGIC I/O».
The «logic digital input close valve» can be configured by ‘Control View’, ‘Control Performance Analyzer’, ‘Universal Hyper
Terminal’ or ‘Service Box 2’.
The «set-command» is: «s:20000000a0».
The «get-command» is: «i:20». The answer returns the «operational settings mode»
Æ
«i:20000000a0».
Description:
code
description
data range
s:20 command
header
a mode
selection 0 = non inverted
1 = inverted
2 = disabled