Installation, Operating & Maintenance Instructions
Series 650 DN 350 (I.D. 14”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
286241EA
2010-10-11
38/86
for Slave valve
Command: s:1012000000<CR><LF>
Answer:
s:10<CR><LF>
Description:
Address allocation for Slave valve #18 (12
hex
).
Screenshot:
•
Address
allocation:
Each valve connected to the valve cluster system must have its unique cluster address. It is possible to address
255 cluster valves. The address allocation is as follows:
Master valve: 00
Slave valves: 01 – FE
hex
Note: If there only one Slave valve the adress must be: 01. If there are more Slave valves, they have to be addressed
from 01, 02, 03,... and so on without gap!
Note: The device address information must be configured when setting up the valve cluster. It is stored in a power
save memory and therefore will be kept even the valve is disconnected from power.