Installation, Operating & Maintenance Instructions
Series 615 DN 40 (I.D. 1.5”), RS485
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
289111EB
2013-02-05
67/96
Setup function
Command
Acknowledgement
(within 10ms after reception of command)
Description
PID CONTROLLER
CONFIGURATION
Set
[s:02][abcdefgh][CR][LF]
[s:02][CR][LF]
Get
[i:02][CR][LF]
[i:02][abcdefgh][CR][LF]
data length 8 characters
a
Controller algorithm:
0
= adaptive downstream (default)
1
= fixed PI downstream control
2
= fixed PI upstream control
3
= soft pump
b
Gain Factor:
0
= 0.10,
1
= 0.13,
2
= 0.18,
3
= 0.23,
4
= 0.32,
5
= 0.42,
6
= 0.56,
7
= 0.75,
8
= 1.00,
9
= 1.33,
A
= 1.78,
B
= 2.37,
C
= 3.16,
D
= 4.22,
E
= 5.62,
F
= 7.50,
G
= 0.0001,
H
= 0.0003,
I
=0.001,
J
= 0.003,
K
= 0.01,
L
= 0.02,
M
= 0.05
c
Sensor Response Time (s):
0
= 0.00,
1
= 0.02,
2
= 0.04,
3
= 0.06,
4
= 0.08,
5
= 0.10,
6
= 0.15,
7
= 0.20,
8
= 0.25,
9
= 0.30,
A
= 0.35,
B
= 0.4,
C
= 0.50,
D
= 0.60,
E
= 0.80,
F
= 1.00
d
Setpoint Ramp Time (s):
0
= 0.0,
1
= 0.5,
2
= 1.0,
3
= 1.5,
4
= 2.0,
5
= 2.5,
6
= 3.0,
7
= 3.5,
8
= 4.0,
9
= 4.5,
A
= 5.0,
B
= 5.5,
C
= 6.0,
D
= 6.5,
E
= 7.0,
F
= 7.5,
G
= 8.0,
H
= 8.5,
I
= 9.0,
J
=9.5,
K
= 10.0
ef
P-Gain:
00
= 0.0010,
01
= 0.0013,
02
= 0.0018,
03
= 0.0024,
04
= 0.0032,
05
= 0.0042
06
= 0.0056,
07
= 0.0075,
08
= 0.010,
09
= 0.013,
10
= 0.018,
11
= 0.024
12
= 0.032,
13
= 0.042,
14
= 0.056,
15
= 0.075,
16
= 0.10,
17
= 0.13
18
= 0.18,
19
= 0.24,
20
= 0.32,
21
= 0.42,
22
= 0.56,
23
= 0.75
24
= 1.0,
25
= 1.3,
26
= 1.8,
27
= 2.4,
28
= 3.2,
29
= 4.2
30
= 5.6,
31
= 7.5,
32
= 10
gh
I-Gain:
00
= 0.0010,
01
= 0.0013,
02
= 0.0018,
03
= 0.0024,
04
= 0.0032,
05
= 0.0042
06
= 0.0056,
07
= 0.0075,
08
= 0.010,
09
= 0.013,
10
= 0.018,
11
= 0.024
12
= 0.032,
13
= 0.042,
14
= 0.056,
15
= 0.075,
16
= 0.10,
17
= 0.13
18
= 0.18,
19
= 0.24,
20
= 0.32,
21
= 0.42,
22
= 0.56,
23
= 0.75
24
= 1.0,
25
= 1.3,
26
= 1.8,
27
= 2.4,
28
= 3.2,
29
= 4.2
30
= 5.6,
31
= 7.5,
32
= 10,
33
= 13,
34
= 18,
35
= 24
36
= 32,
37
= 42,
38
= 56,
39
= 75,
40
= 100
Note:
In adaptive downstream mode ef (set 00) and gh (set 00) are not used.
In fixed PI modes b (set 0) and c (set 0) are not used.
In pump down mode bc (set 00) and gh (set 00) are not used.
This command selects gain factor, sensor response time and setpoint ramp for the PID
controller.
Note:
Refer to «Tuning of control performance» for details.