3.11.2 Tuning of pressure control performance with fixed PI control
Normally the default settings will result in good pressure control performance. For some applications tuning may be
required to improve performance.
The tuning procedures for each parameter (grey boxes) and its default values are described separately below. Strictly
keep the order of the procedure.
No
No
P-Gain to
adjustment /
optimizing
Pressure
control
ok ?
Start
End
Contact
VAT
Pressure
control
ok ?
Set P-Gain / I-Gain to
default value and valve
speed to maxium
Yes
I-Gain to
adjustment /
optimizing
Yes