Tank Gate Interface
70
Installation and Operations Manual
5.8.2
Application
The MFPREG point continually scans Modbus slave devices, using the ID parameter. Chan
determines which 8203 Dual RS-485 Communications Interface Module Channel is used for
communications to the slave device. An MFPREG point is needed for each device connected to
the 8303 TGI. Up to 64 registers may be read with each MFPREG point. Multiple MFPREG points
can be used with a single slave device if necessary. The BaudRate and ComParams values must
match the communications parameters of the slave device. The communications parameters are
set as each MFPREG point is processed. This allows slaves with different baud rates and data link
settings to exist on the same bus (not recommended).
8203 TGI software points may begin scanning when the point is created, or when the correct
Channel number is assigned. Which of these events begins the scanning process varies with
each point.
A total of four blocks may be read or written. The ReadCmd determines the command to read
data and the WriteCmd is the command used for write operations. The Addr and Size parameters
determine the addresses. Set the Addr1 and Size1 parameters to read a data block from the slave
device. The response will be placed in the Value0 - Value63 parameters. For example, if Addr1
= 100 and Size1 = 10, then the MFPREG point will read 10 register values and place the data in
Value0 - Value9. If a second block is defined, then the data response will start in Value10. If the
Size is 0, then that block is disabled.
The Mode parameter can be used to swap the byte order of the floating point values.
Dynamic Parameters
Function
Value0
Value63
Register values from slave device. Value0 will always correspond to the
first register read from the slave device using the Addr1 and Size1
parameters. You can read up to 64 registers from the slave device. The
meaning of the Value array depends upon the definition of the blocks.
PntStatus
Byte value indicating status of point Values are:
0x0000: No Error
0x0001: No Response from Device
Elapse
Time of the last request from the master
PntCheckSum
CRC-16 Checksum of point's static Configuration Parameters
Summary of Contents for 8300 series
Page 2: ......
Page 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Page 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Page 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Page 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Page 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Page 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Page 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Page 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Page 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Page 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Page 149: ......