Tank Gate Interface
52
Installation and Operations Manual
5.3.2
Application
The GSIME point provides an interface to GSI Model 2000 Tank Gauge Transmitters. Tank gauges
are connected directly to a 8303 Dual RS-485 Communications Interface Module. The ID must
match the unit address of the GSI transmitter and the Baud Rate must match the Baud Rate of
the gauge.
The DataMode must match the engineering units of the gauge. Conversion from Metric to
English (or vice-versa) can be performed be setting the LevelConvert and the TempConvert
parameters in the MODSCAN point associated with the GSIMB point. The Level can be offset by
entering a value for the LevelOffset parameter. The LevelOffset is added to the Level after any
conversion have be performed. Likewise, the TempOffset can be used to provide a temperature
offset.
Dynamic Parameters
Function
Level
IEEE Floating point value representing the tank level. The data is returned
in the format specified during the configuration of the gauge.
Temp
Floating point value representing the product temperature. The data is
returned in the format specified during the configuration of the gauge.
PntStatus
Byte value indicating status of point. Values are:
0x0000: No Error
0x0001 No Response from transmitter
0x0002: Data is invalid
0x0004: Command Timeout
0x8000: Gauge did not response to last request (pre-fail)
GaugeStatus
Byte value indicating status of the gauge. Refer to the transmitter manual
for details on the
GaugeStatus
Reserved
Reserved.
Reserved2
Reserved Value (32 bit Register 0048)
Elapse
Time of the last scan
Interval
Amount of time (in HR:MIN:SEC) between scans of the gauge
PntCheckSum
CRC-16 Checksum for point’s static Configuration Parameters.
Summary of Contents for 8300 series
Page 2: ......
Page 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Page 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Page 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Page 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Page 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Page 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Page 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Page 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Page 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Page 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Page 149: ......