5.15 Ronan X76CTM (X76CTM)
The X76CTM point provides an interface to the Ronan X76CTM tank monitoring system. This
point provides both level and temperature data. Information such as volume, leak rate, point
and gauge status, is also available in this point block.
5.15.1 Parameters
The database parameters used by the X76CTM point are listed and described below:
Config Parameters
Function
Tag
A Tag can contain 15 bytes of data and can include any printable ASCII
character. Tags can be used to identify points indicating the use of the
point such as “Tank 22.” The default tag is set to “X76CTM.00”.
Description
The point description can contain 30 bytes of data and can include any
printable ASCII character. Descriptions can be used as information
relevant to any aspect of the point, such as its use, location, operating
information, etc. The default description is set to “X76CTM.00”.
Module
Valid values 1-4. Default value is 255.
Chan
Communications channel to which the gauge is connected. For an 8203
Dual RS-485 Communications Interface Module Chan is either 1 or 2.
BaudRate
8203 Dual RS-485 Communications Interface Module: Valid values are:
2400, 4800, and 9600. The default is 9600.
ComParams
Defines the number of data bits and the parity used by the com port.
Valid values include:
8N - 8 data bits, No parity
8O - 8 data bits, Odd parity
8E - 8 data bits, Even parity
7O - 7 data bits, Odd parity7E - 7 data bits, Even parity
The default is 8N.
ID
Ronan System Modbus Address
cTankNumber
Tank Number in the Ronan System
LevelConvert
Determines the units in which the level data will be displayed.
F: Feet
m: millimeters
Default is I.
TempConvert
Determines the units in which the temperature data will be displayed.
F: Fahrenheit
C: Celsius
If no value is specified, no conversion will be performed. The default is
F.
TempDeadband
The TempDeadband is used to set the Change Of State deadband for
temperature. The default is .25 degrees.
LevelDeadband
The LevelDeadband sets the deadband for the Change of State mode.
The default is 0.001.
Summary of Contents for 8300 series
Page 2: ......
Page 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Page 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Page 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Page 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Page 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Page 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Page 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Page 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Page 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Page 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Page 149: ......