Tank Gate Interface
62
Installation and Operations Manual
allows slaves with different baud rates and data link settings to exist on the same bus (this
practice is allowed but not recommended).
The MBTX point scans the following Modbus data from the 4000 ATT:
It is possible to calibrate the ATT from the MBTX point. Set the LevelRef to the desired level in
the tank. Issue a Calibrate command (set the Command parameter to Calibrate). The Level will
be offset by the LevelRef.
Command
Address
Data
# of Registers
65
0
Level, Temp
2 Floating point
4
5
AlmStat, DiagStat
2 Integers
65
21
Level Reference
1 Floating point