Tank Gate Interface
92
Installation and Operations Manual
Report
Causes automatic notification to the Host (in response to a Change of State
Request) when a Value Changes State. Parameter values can be High, Low or No.
Report=No disables notification. Points with Report= High will be sent before
points with Report = Low. Default is High.
Maxtime
Specifies the maximum time (in secs) between automatic Change of State
responses being sent to the Host. Report must be set to either Low or High for the
Value parameter to be sent in response to a Change of State Request. A value of 0
disables this option. Non-zero values cause responses to be sent even if the value
has not changed since the last message. The maximum is 65535 seconds. The
default is 600.
Watchdog
Enables the watchdog task on the Motherboard. The watchdog task monitors the
TSM point on the 8303 Dual RS-485 Communications Interface Module and
verifies it is scanning for gauges.
Dynamic Parameters
Function
Level
IEEE Floating point value representing the tank level. The data is returned in the
format specified during the configuration of the gauge.
Level1
Floating point value representing the uncorrected Tank Level.
Temp
Floating point value representing the product temperature. The data is returned
in the format specified during the configuration of the gauge.
TopPress
Floating Point value representing the Top Pressure
MidPress
Floating Point value representing the Middle Pressure
BotPress
Floating Point value representing the Bottom Pressure
Density
Floating point value representing the density.
Water Level
Floating point value representing the Bottom Water level
AmbientTemp
Outside Air Temperature.
Device Status
TSM Internal Status. See the TSM documentation for more information.
Analog1
4 to 20 mA value %
VaporTemp
Air/Gas Temperature
Value
Digital Inputs Value.
Config/Constant
Parameters
Function
Summary of Contents for 8300 series
Page 2: ......
Page 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Page 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Page 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Page 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Page 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Page 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Page 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Page 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Page 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Page 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Page 149: ......