8-5/8”
(219 mm)
2-13/16”
(71 mm)
7-3/8”
(188 mm)
8-3/8”
(213 mm)
Gas line stub
1/2” male npt
Electrical access/
Junction box
Rear of
appliance
5. Remove the 4 screws retaining the appliance to its
pallet. Snap o
ff
the feet attached to the pallet and
discard or recycle.
6. With great care not to cut yourself on the sharp feet,
set the appliance
partially
into the framing keeping
in mind the need to access the rear of the appliance
to connect the electrical wires.
Installation
Left side view
Set-up Gas Supply
The gas supply inlet connection is a 1/2” NPT male line
stub located on the rear left hand side of the appliance.
The unit is supplied with a stainless steel
fl
ex line to
allow the appliance to be disconnected for service. An
individual shut-o
ff
valve (supplied) is required on the
supply line ahead of the
fl
ex connector.
Use only new black iron or steel pipes, CSST, or copper
tubing if acceptable—check local codes. Note that
in USA, copper tubing must be internally tinned for
protection against sulfur compounds.
Unions in gas lines should be of ground joint type.
The gas supply line must be sized and installed to
provide a supply of gas su
ffi
cient to meet the maximum
demand of the appliance without undue loss of
pressure.
Sealant used must be resistant to the action of all gas
constituents including LP gas. Sealant should be applied
lightly to male threads to ensure excess sealant does
not enter gas lines.
Gas Supply