83
Install Plenum Kits (LDK1, LDK3 & LDK4)
—see next page for LDK7 Duct Termination
Plates
1. Frame a rough opening at the desired location—see
earlier sections of this manual for allowable plenum
positions and rough frame opening sizes.
2. Install top mounting bracket(s) to the plenum using
screws provided (use the short sheet metal screws
provided otherwise the screw tails (ends) will inter-
fere with the
ȴ
nishing frame when installed).
3. Install the plenum(s) into the rough frame opening
maintaining minimum clearances to combustibles
as listed—see page 10. Fix the plenum to the fram-
ing using nails or screws through the top mounting
bracket.
Note that the mounting brackets are not
intended to carry the weight of the plenum and
pipes. Provide support to the underside of the
plenum and ensure the plenum is level and its
outlet is not distorted (see detail on page 11).
Use
metal strapping (all-round, not supplied) as required
to further secure the plenum to framing.
4. Attach one section of UL-181, Class 1 approved air
duct to each of the collars and secure it with gear
clamps provided.
DO NOT SPLICE DUCTS!
5. Attach the top of the pipe sections to the plenum
securing them with the gear clamps provided. An
upward slope must be maintained in horizontal sec-
tions of pipes for proper convection. Use straps as
necessary to maintain the pipes positions. Support
horizontal sections every 24 inches.
6. Paint the inside surfaces of the plenum using high-
temperature
ȵ
at black spray paint for installations
where the inside of the plenums may be visible.
Note:
The
ȵ
anges of the white
ȴ
nishing frame (when
used) will insert approximately 1-1/4” into the ple-
num covering the shiny sheet metal.
7. Install the
ȴ
nishing frame or louver to the plenum
after the wall
ȴ
nish is completed:
LDK1, LDK4:
Use the LDK2 or LDK5 depending of the
length of the plenum.
LDK3:
Use the grilles provided with the kit.
Note:
The frame/louver are
ȴ
nished white but
may be painted another color if desired; use high
temperature paint (250
º
F). You may also
ȴ
nish
up to the perimeter of the plenum opening with
your material of choice and not use the frame or
louver. Do not
ȴ
nish over any of the opening in
the plenum outlet.
8. Continue with the
ȴ
replace installation.
Ʉ
WARNING
A l l F O U R ( 4 ) t a k e o f f s M U S T B E
C O N N E C T E D T O P L E N U M ( S ) .
Appendix D - HeatShift
®
Installation