Valve assembly
Pressure testing
Manifold pressure adjustment
behind plastic cap
Control Valve
Valve inlet
pressure
Manifold
test
pressure
Receiver
Flexible connector
supplied with unit
Valve cover on
front of the
appliance
Caution
Never use an open flame to check for leaks!
Correct any leak detected immediately.
Gas Supply
Pressure Test Points
The minimum supply pressure is given in the section
Speci
fi
cations
of this manual—page 6.
All piping and connections must be tested for leaks af-
ter installation or servicing. All leaks must be corrected
immediately.
When testing for leaks:
• Make sure that the appliance is turned o
ff
.
• Open the manual shut-o
ff
valve.
• Test for leaks by applying a liquid detergent or soap so-
lution to all joints. Bubbles forming indicate a gas leak.
The pressure test tapping locations are shown in the
fi
gure below. An internal regulator within the valve
controls the burner manifold pressure.
The correct pressure range is shown in the table in
section
Speci
fi
cations
of this manual on page 6. The
pressure check should be made with the burner alight
and at its highest setting. See Appendix A - Lighting
Instructions Plate on page 74 in this manual for full
operating details.