25
43”
20-1/8”
57-3/4”
1/2” thick non-combustible
cement board required above,
on each side and below
engine opening (NOT supplied)
NOTE: Height of cavity may be
affected by vent configuration
- see page 26
Between underside
of header and bottom
of firebox
No hearth required.
If using a hearth,
see page 22.
NOTE: This unit requires a
solid platform to support it.
Combustible framing allowed
beneath fireplace. When the
appliance is installed directly
on carpeting, tile or other
combustible material other
than wood flooring, the
appliance shall be installed
on a metal or wood panel
extending the full width
and recessed depth of the
appliance
NON-COMBUSTIBLE MATERIALS ONLY
READ INSTRUCTIONS
MATÉRIAUX INCOMBUSTIBLES SEULEMENT
CONSULTEZ LE GUIDE D’INSTALLATION
NON-COMBUSTIBLE MATERIALS ONLY
READ INSTRUCTIONS
MATÉRIAUX INCOMBUSTIBLES SEULEMENT
CONSULTEZ LE GUIDE D’INSTALLATION
Min. 60” (1524 mm)
50” (1270 mm)
M
in. 44-1/2”
(1130 mm)
M
in.
20-1/2”
(521 mm)
14-3/4”
(375 mm)
M
in.
9-1/4”
(235 mm)
Min. 5”
(127 mm)
Min. 5”
(127 mm)
Flush with bottom of unit;
add extra cement board
if overlapping framing.
Joints preferred at corners
to prevent cracking
Minimum coverage area of non-combustible cement board.
Any
wall
finish applied to shaded area must be non-combustible.
Linear 1700 fireplace
outline (including
stand-offs)
Non-combustible
cement board
required
thickness:
1/2 inch (13 mm)
NON-COMBUSTIBLE MATERIALS ONLY
READ INSTRUCTIONS
MATÉRIAUX INCOMBUSTIBLES SEULEMENT
CONSULTEZ LE GUIDE D’INSTALLATION
27
23.
Note: If using optional
LDK Duct Kit, refer
to LDK instructions
packed with kits as
framing is affected.
Framing Requirements
Framing Dimensions
Minimum Cement Board Dimensions
QUALIFIED
INSTALLER