4.3.2 Over Temperature Alarm
The Over Temperature Alarm is relative to the temperature setpoint of
each zone.
The over temperature alarm tolerance is the number of degrees that
any zone can heat above its temperature setpoint before triggering an
over temperature alarm.
If any zone goes into Over Temperature Alarm, the heaters of the
affected zone are automatically shut off.
The over temperature alarm tolerance range is 9°F to 108°F (5°C to
60°C). The factory default setting is 45°F (25°C).
This parameter can be accessed in Password Level 2 or higher.
X4