Installation instructions geoTHERM VWS/VWW 0020051574_01
8.8
Displays in the code layer
The Code layer has different areas in which you can
change parameters or merely view them, depending on
the context. The context can always be recognised from
the menu name.
Menu C: Set parameters for the heating system
Menu D: Perform diagnostics
Menu I: Display general information
Menu A: Installation assistant
Your code entry is reset again 15 minutes after your last
change in the Code level (actuation of one of the dials).
To gain entry to the Code level again after that, you will
have to enter the code once more.
Display shown
Description
Factory setting
Menu C: Set parameters for the heating
system
In Menus C1 to C9 you can set the parameters for
the various functions of the heat pump.
Code layer
C1
change
Code number:
> 0 0 0 0
Accept change?
No
> Set figures
Menu for changing the code number.
You can replace the standard code 1000 with a user-
defined four-digit code here.
Note:
If you change the code, make a note of the
new code, otherwise you will not be able to make
any more changes in the code level!
1000
HK2
C2
Parameters
Type
direct circuit
Heating curve
0.80
Max limit outs. temp.
21 °C
Comp. starts at
-120 °min
> Settable values
Type:
Direct circuit (for direct hydraulics),
Mixer circuit (for buffered hydraulics),
Fixed value (can only be set via vrDIALOG 810/2).
Heating curve:
Adjustable heating curve (not with
fixed value).
Maximum limit outside temperature:
Temperature
limit for switching off heating mode (summer func-
tion).
Comp. Start:
Set the degree minutes until compres-
sor start (only with direct hydraulics)
0.3
22 °C
HK2
C2
Parameters
Type
Fixed value
Max limit outs. temp.
21 °C
> Settable values
This display appears if "Fixed value" has been set via
vrDIALOG 810/2.
If a VR 60 is connected, this menu appears several
times (for each heating circuit).
Buffer tank
C3
Information
Setpoint flow temp.
41 °C
T buffer top VF1
29 °C
T Buff. Bot OffsetRF1
25 °C
This display is only shown when a buffer cylinder is
used (e.g. Hydraulic Plans 2 and 4).
Setpoint flow temp.:
Target flow temperature
T buffer top VF1:
Temperature at the buffer cylin-
der top sensor VF1
T Buff. Bot. Offset RF1:
Temperature at the buffer
cylinder bottom sensor RF1 (see Section
8.4.3
)
Table 8.4 Parameters that can be set in the Code level
Controller 8