vacon 50x parameters
vacon
62
24-hour s358 (0)40 837 1150 • Email: [email protected]
7
Parameter 109, Power On Hours, displays how long the drive has been powered up.
Parameter 110, Stator Frequency, displays the frequency the drive is applying to the mo-
tor stator.
Parameter 111, DC Bus Voltage, displays the voltage on the DC bus.
This parameter displays the power being output by the drive in terms of drive rating. The
measurement is calculated by scaling the Load Torque value by the ratio of Volt-Amps to
Rated Volt-Amps, and adjusted by Output Frequency.
Parameter 201, the Input Mode parameter, configures local and remote control of the
Start/Stop source and the reference source.
The following data values may be assigned to this parameter:
Parameter Value
Run/Stop Control
Local only
Local keypad operation only
Remote only
Terminal strip operation only
L/R Rem Ref
LOCal Keypad Start/Stop and Speed
REMote Keypad Start/Stop, Terminal Strip Speed Reference
L/R Rem Ctl
LOCal Keypad Start/Stop and Speed
REMote Keypad Speed Reference, Terminal Strip Start/Stop
L/R Rem Bth
LOCal Keypad Start/Stop and Speed
REMote Terminal Strip Start/Stop and Speed Reference
EMOP
{1} {2} {4}
Terminal strip operation using Increase/Decrease buttons
EMOP2
{1} {3} {4}
Terminal strip operation using Increase/Decrease buttons
LOC/EMOP
{1} {2} {4}
LOCal Keypad Start/Stop and Speed
REMote Terminal strip operation using Increase/Decrease
LOC/EMOP2
{1} {3} {4}
LOCal Keypad Start/Stop and Speed
REMote Terminal strip operation using Increase/Decrease
NOTES:
1.
Electronic Motor Operated Potentiometer (EMOP): simulates the INC/DEC keys on
keypad using external remote N/O pushbuttons
2.
Commanded output frequency returns to the value of parameter 301 (Min Frequen-
cy) when the drive is stopped.
3.
Commanded output frequency remains at the previous setpoint when the drive is
stopped.
4.
The parameters that set the functions of the designated digital inputs for EMOP
must be configured as “EMOP+” and “EMOP–” to complete the implementation.
109 Power On Hours
Read-Only
Range: 0–65535 h
Level 2
110 Stator Freq
Read-Only
Range: 0.0–400.0 Hz
Level 2
111 DC Bus Voltage
Read-Only
Range: 0–1000 Vdc
Levels 1, 2
115 Drive Power Out
Read-Only
Range: 0.0–200.0%
Level 2
201 Input Mode
Default = Local only
Range: Text string
Levels 1, 2
Summary of Contents for 50X
Page 1: ......
Page 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Page 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Page 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Page 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Page 132: ......