vacon 50x parameters
vacon
88
24-hour s358 (0)40 837 1150 • Email: [email protected]
7
This parameter defines the protocol and the parity of the SIO port.
The following data values may be assigned to this parameter:
Parameter Value
Description
RTU N81
No parity, 8 data bits, 1 stop bit
RTU N82
No parity, 8 data bits, 2 stop bits
RTU E81
Even parity, 8 data bits, 1 stop bit
RTU O81
Odd parity, 8 data bits, 1 stop bit
This parameter defines the baud rate of the SIO port.
The following data values may be assigned to this parameter:
Parameter Value
4800
9600
19200
38400
57600
This parameter defines the network drop number for both SIO and IRDA communica-
tions.
This parameter defines a watchdog timer that will require a valid communication in the
specified time period while in SIO control. If the requirement is not met, a fault occurs.
900 SIO Protocol
Default: RTU N81
Range: Text string
Level 2 (SIO)
901 SIO Baud Rate
Default: 9600
Range: Text string
Level 2 (SIO)
902 Comm Drop #
Default: 1
Range: 1–247
Level 2 (SIO)
903 SIO Timer
Default: 1.0 sec
Range: 0.0–60.0 sec
Level 2 (SIO)