81
vacon
vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
Running REV
The motor is running in Reverse and the output frequency is
above 0.5 Hz.
Zero Speed
The drive is in Run mode, but the speed reference is 0 Hz.
At Speed
The drive has reached reference speed.
Freq Limit
The drive limit is active when the speed commanded exceeds
the value of parameter 306, Preset Freq 4.
Freq Hyst
This is active when the speed exceeds parameter 306 (Preset
Freq 4) but is less than parameter 307 (Preset Freq 5).
Current Lim
Current Limit mode is active.
High Temp
The temperature limit of the drive has been exceeded.
Local Mode
The keypad is the control path for reference speed and control
functions.
SeqOut-00
Programmed sequence step active. SeqOut-00, SeqOut-01,
SeqOut-01
SeqOut-10, SeqOut-11 are all status outputs linked to a step in
SeqOut-10
the program sequencer.
SeqOut-11
See
on page
more information.
ARCTIC
When a digital output is configured to use this option, the out-
put will be active when the Arctic Mode is turning on the DB
resistor.
This option will turn on when the temperature drops below the
Arctic mode entry point, which is –7 degrees C. This will work
even if Arctic Mode is not enabled.
Ref Loss
Independent of the status of parameter 222 (Ref Loss Config),
this selection activates the digital output when a 4-20mA input
to either the VIN1 or CIN inputs drop to approximately 3mA.
This parameter configures the input state of all the digital inputs except the EN digital in-
put. The EN digital input is always active high. The following data values may be assigned
to this parameter:
Parameter Value
Description
Active Low
Low input is true (“pull-down logic”)
Active High
High input is true (“pull-up logic”)
These parameters configure the function that the digital inputs DI1–5 will perform when
active. The following data values may be assigned:
Parameter Value
Description
Preset 1
Preset Speed Input 1 (PS1).
Preset 2
Preset Speed Input 2 (PS2).
Preset 3
Preset Speed Input 3 (PS3).
Coast Stop
Activates a Coast-to-Stop condition.
DC Inject
Begins DC injection braking.
Loc/Rem
Switches from Local to Remote mode.
Alt Ramp
Activates Alternate Ramp.
Fault Reset
Resets a fault.
720 Active Logic
Default: Active High
Range: Text string
Level 2
721 DI1 Configure
722 DI2 Configure
723 DI3 Configure
724 DI4 Configure
725 DI5 Configure
Default: Preset 1
Default: Preset 2
Default: Preset 3
Default: Alt Ramp
Default: Fault Reset
Range: Text string
Level 2
Summary of Contents for 50X
Page 1: ......
Page 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Page 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Page 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Page 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Page 132: ......